§ 113.43-5 - Power supply.

Each steering failure alarm system must be supplied by a circuit that:

(a) Is independent of other steering gear system and steering alarm circuits;

(b) Is fed from the final emergency power source through the emergency distribution panel in the wheelhouse, if installed; and

(c) Has no overcurrent protection except short-circuit protection by an instantaneous fuse or circuit breaker rated or set at 400 to 500 percent of:

(1) The current-carrying capacity of the smallest alarm system interconnecting conductors; or

(2) The normal load of the system.

authority: 46 U.S.C. 3306,3703; DHS Delegation No. 00170.1, Revision No. 01.2
source: CGD 74-125A, 47 FR 15272, Apr. 8, 1982, unless otherwise noted.
cite as: 46 CFR 113.43-5