(a) The longitudinal joint factor to be used in the design formula in § 192.105 is determined in accordance with the table 1 to this paragraph (a):
Specification
| Pipe class
| Longitudinal
joint factor
(E)
|
---|
ASTM A53/A53M (incorporated by reference, see § 192.7) | Seamless | 1.00
|
| Electric resistance welded | 1.00
|
| Furnace butt welded | .60
|
ASTM A106/A106M (incorporated by reference, see § 192.7) | Seamless | 1.00
|
ASTM A333/A333M (incorporated by reference, see § 192.7) | Seamless | 1.00
|
| Electric resistance welded | 1.00
|
ASTM A381 (incorporated by reference, see § 192.7) | Double submerged arc welded | 1.00
|
ASTM A671/A671M (incorporated by reference, see § 192.7) | Electric-fusion-welded | 1.00
|
ASTM A672 (incorporated by reference, see § 192.7) | Electric-fusion-welded | 1.00
|
ASTM A691/A691M (incorporated by reference, see § 192.7) | Electric-fusion-welded | 1.00
|
API Spec 5L (incorporated by reference, see § 192.7) | Seamless | 1.00
|
| Electric resistance welded | 1.00
|
| Electric flash welded | 1.00
|
| Submerged arc welded | 1.00
|
| Furnace butt welded | .60
|
Other | Pipe over 4 inches (102 millimeters) | .80
|
Other | Pipe 4 inches (102 millimeters) or less | .60 |
(b) If the type of longitudinal joint cannot be determined, the joint factor to be used must not exceed that designated for “Other.”