§ 1304.100 - Scope and intent.

This subpart prescribes requirements for floating cabins on the Tennessee River System. Floating cabins as applied to this subpart include existing nonnavigable houseboats approved by TVA and other existing structures, whose design and use is primarily for human habitation or occupation and not for navigation or transportation on the water. Floating cabins that were not located or moored on the Tennessee River System as of December 16, 2016, shall be deemed new floating cabins. New floating cabins are prohibited and subject to the removal provisions of this part and Section 9b of the TVA Act. No new floating cabins shall be moored, anchored, or installed on the Tennessee River System. Floating cabins that were located or moored in the Tennessee River System as of December 16, 2016, shall be deemed existing floating cabins. Existing floating cabins may remain moored on the Tennessee River System provided they remain in compliance with the rules in this part and obtain a permit from TVA issued after October 12, 2021. All permits for nonnavigable houseboats or floating cabins that were not located on the Tennessee River System as of December 16, 2016, are terminated. Unless otherwise noted, the term floating cabin refers to the primary structure on the monolithic frame as well as all attached structures.

[86 FR 50633, Sept. 10, 2021]
§ 1304.101 - Floating cabins.

(a)(1) Floating cabins include nonnavigable houseboats approved by TVA as of December 16, 2016, and other floating structures moored on the Tennessee River System as of this date and determined by TVA in its sole discretion to be designed and used primarily for human habitation or occupation and not designed and used primarily for navigation or transportation on the water as of December 16, 2016. If, at any time, the floating cabin is modified such that it no longer meets the criteria to be deemed a floating cabin, the approval for that existing floating cabin will be terminated. TVA's judgment will be guided by, but not limited to, the following factors:

(i) Whether the structure is usually kept at a fixed mooring point;

(ii) Whether the structure is actually used on a regular basis for transportation or navigation;

(iii) Whether the structure has a permanent or continuous connection to the shore for electrical, plumbing, water, or other utility service;

(iv) Whether the structure has the performance characteristics of a vessel typically used for navigation or transportation on water;

(v) Whether the structure can be readily removed from the water;

(vi) Whether the structure is used for intermittent or extended human-habitation or occupancy;

(vii) Whether the structure clearly has a means of propulsion, and appropriate power/size ratio;

(viii) Whether the structure is safe to navigate or use for transportation purposes.

(2) That a structure could occasionally move from place to place, or that it qualifies under another federal or state regulatory program as a vessel or boat, are factors that TVA also will consider but would not be determinative. Floating cabins are not recreational vessels to which § 1304.409 applies.

(b) Owners of floating cabins are required to register the floating cabin with TVA by January 10, 2022. Floating cabin owners shall include the following information with their registration: Clear and current photographs of the structure; a drawing or drawings showing in reasonable detail the size and shape of the floating cabin (length, width, and height) and attached structures, such as decks or slips (length, width, and height); and a completed and signed TVA registration form. The completed TVA registration form shall include the mailing and contact information of the owner(s); the TVA permit or TVA-issued numbers (when applicable); the mooring location of the floating cabin; how the floating cabin is moored; how electrical service is provided; how wastewater and sewage are managed; and an owner's signature.

(c) All floating cabins shall comply with the rules contained in this part and make application for a section 26a permit by October 1, 2024.

(d) Existing floating cabins may remain on the Tennessee River System provided they stay in compliance with the rules contained in this part and pay any necessary and reasonable fees levied by TVA to ensure compliance with TVA's regulations, in accordance with section 9b of the TVA Act.

(e) Existing floating cabins must be moored at one of the following locations:

(1) To the bank of the reservoir at locations where the owner of the floating cabin is the owner or lessee (or the licensee of such owner or lessee) of the proposed mooring location provided the floating cabin was moored at such location as of December 16, 2016;

(2) At locations described by § 1304.201(a)(1), (2), and (3) provided the floating cabin was moored at such location as of December 16, 2016;

(3) To the bank of the reservoir at locations where the owner of the floating cabin obtained written approval from TVA pursuant to subpart A of this part authorizing mooring at such location as of December 16, 2016; or

(4) Within the designated and approved harbor limits of a commercial marina that complies with § 1304.404. As provided in § 1304.404, TVA may adjust harbor limits and require relocation of an existing floating cabin within the harbor limits.

(f) Applications for mooring of a floating cabin outside of designated harbor limits will be disapproved if TVA determines that the proposed mooring location would be contrary to the intent of this subpart.

(g) A floating cabin moored at a location approved pursuant to this subpart shall not be relocated and moored at a different location without a permit from TVA, except for movement to a new location within the designated harbor limits of the same commercial marina. Existing floating cabins may only relocate to the harbor limits of a commercial marina that complies with § 1304.404 on the same reservoir where the floating cabin was moored as of December 16, 2016. Relocation of a floating cabin to another TVA reservoir is prohibited.

(h)(1) Existing floating cabins shall be maintained in a good state of repair and may be maintained without additional approval from TVA. By way of example, these activities may include painting, changing the internal walls within the existing enclosed space, replacing the shingles, siding, electrical wiring, or plumbing, or adding new flotation in compliance with § 1304.400. Repair and maintenance activities shall not modify the dimensions (length, width, and height) of the floating cabin, any external walls, or the enclosed or open space.

(2) Any alterations to the dimensions or approved plans for an existing floating cabin shall be deemed a structural modification and shall require prior written approval from TVA. All expansions in length, width, or height are prohibited, except under the following circumstances if approved in writing in advance by TVA:

(i) TVA may allow alterations necessary to comply with health, safety, and environmental standards;

(ii) TVA may allow changes in roof pitch or allow open portions of the monolithic frame to be covered, but no part of the floating cabin may exceed a total height of 14 feet above the lowest floor level; or

(iii) TVA may allow enclosure of existing open space on the monolithic frame of the existing floating cabin if the enclosure will not result in expansion to the dimensions (length, width, and height) of the monolithic frame, subject to § 1304.101(i). At least 24 contiguous square feet of open space with a minimum width of four feet shall be maintained on the monolithic frame for unrestricted boarding.

(3) Owners must submit an application to TVA 60 days in advance of proposed rebuilding of a floating cabin or a significant portion of a floating cabin. The owner shall not begin construction until prior written acknowledgment from TVA is received. Plans for removal of the existing floating cabin or portions to be rebuilt shall be acknowledged in writing by TVA before removal occurs, and the removal shall be at the owner's expense before construction of the rebuild may begin. The owner shall provide evidence of approval from the marina operator to rebuild within the marina. TVA may require a new permit for the proposed rebuilding. Construction of the rebuilt floating cabin must be completed within 18 months. The rebuilt floating cabin shall match the exact configuration and dimensions (length, width, and height) of both the total floating cabin and the enclosed and open space as approved by TVA; attached structures are subject to § 1304.101(i).

(4) TVA may allow the exchange of multiple existing floating cabins removed from the Tennessee River System for a single combined floating cabin under the following conditions:

(i) Prior written approval from TVA shall be obtained before taking any actions. Evidence shall be provided to TVA that all existing floating cabins to be exchanged were located on the Tennessee River System as of December 16, 2016.

(ii) Plans for removal of the existing floating cabin(s) shall be approved in writing by TVA before removal occurs, and the floating cabin(s) shall be removed at the owner's expense before construction of the new combined floating cabin may begin. Approvals of the existing floating cabins to be exchanged will be terminated. Construction on the new combined floating cabin must be completed within 18 months.

(iii) The combined floating cabin shall be moored within the harbor limits of a commercial marina that complies with § 1304.404. The owner shall provide evidence of approval from the marina operator to locate within the marina. The combined floating cabin must be located on the same reservoir as any of the existing floating cabins to be exchanged.

(iv) The maximum total size of the monolithic frame of the combined floating cabin is 1,000 square feet or the sum of the square footage of the monolithic frames of the existing exchanged floating cabins, whichever is less. At least 24 contiguous square feet with a minimum width of four feet must remain open to allow for unrestricted boarding of the combined floating cabin. Any square footage of the existing exchanged floating cabins that exceeds the maximum allowable total size of the combined floating cabin is not transferrable to other projects or owners.

(v) The maximum height of any part of the combined floating cabin is 14 feet above the lowest floor level.

(vi) Floating attached structures, such as decks or platforms, are subject to § 1304.101(i).

(i) With written approval from TVA, floating cabins may be accompanied by floating attached structures subject to the following:

(1) A single floating cabin may have multiple floating attached structures. The footprint of each attached structure will be measured as a rectangular or square area. The total footprint of all attached structures for a single floating cabin cannot exceed 400 square feet or the total footprint of the existing attached structures that were part of the floating cabin as of December 16, 2016, whichever is greater.

(2) The footprint of the attached structures shall not be incorporated into the footprint of the monolithic frame of the floating cabin.

(3) Attached structures shall not exceed 14 feet in height from the lowest floor level, shall not be enclosed, and shall comply with § 1304.204(p).

(4) All attached structures must be permitted to the floating cabin owner. The owner shall provide evidence of approval from the marina operator for the attached structures.

(5) Existing attached structures that were part of the floating cabin as of December 16, 2016, may remain with written approval from TVA. Any requests to rebuild or reconfigure attached structures must comply with § 1304.101(i)(1) through (4). Attached structures associated with a request for a structural modification as described in § 1304.101(h)(2)(iii) or a combined floating cabin as described in § 1304.101(h)(4) shall not exceed a total footprint of 400 square feet.

(j) Any floating cabin not in compliance with this part is subject to the applicable removal provisions of § 1304.406 and section 9b of the TVA Act.

[86 FR 50633, Sept. 10, 2021]
§ 1304.102 - Numbering of floating cabins and change in ownership.

(a) All approved floating cabins and attached structures shall display a number assigned by TVA. The owner of the floating cabin shall paint or attach a facsimile of the number on a readily visible part of the outside of the facilities in letters at least three inches high. If TVA provided a placard or tag, it must be displayed on a readily visible part of the outside of the floating cabin.

(b) When there is a change in ownership of the floating cabin, the new owner shall notify TVA within 60 days. Upon application to TVA by the new owner, the new owner may continue to use the existing floating cabin or carry out permitted activities pending TVA's decision on reissuance of the permit. TVA shall reissue the permit upon determining the floating cabin is in good repair, is the same configuration and dimensions (length, width, and height) of both the floating cabin and the enclosed and open space as previously permitted, moored in the same location or in the harbor limits of the same commercial marina, and complies with the conditions of the previous approval and the requirements of this subpart.

[86 FR 50635, Sept. 10, 2021]
§ 1304.103 - Health, safety, and environmental standards.

(a) Wastewater. Floating cabins shall comply with § 1304.2(d) with regard to discharges into navigable waters of the United States. All discharges, sewage, and wastewater, and the pumping, collection, storage, transport, and treatment of sewage and wastewater shall be managed in accordance with all applicable federal, state, and local laws and regulations. If a floating cabin is documented to be in violation of any federal, state, or local discharge or water quality regulation by the respective regulatory agency, TVA is authorized to revoke the permit and require removal of the floating cabin from the Tennessee River System if the violation is not corrected as specified by the regulatory agency in accordance with the agency's requirements.

(b) Flotation. Floating cabins shall comply with the requirements for flotation devices and material contained in § 1304.400.

(c) Mooring. All floating cabins must be moored in such a manner as to:

(1) Avoid obstruction of or interference with navigation, flood control, public lands, or reservations;

(2) Avoid adverse effects on public lands or reservations;

(3) Prevent the preemption of public waters when moored in permanent locations outside of the approved harbor limits of commercial marinas;

(4) Protect land and land rights owned by the United States alongside and subjacent to TVA reservoirs from trespass and other unlawful and unreasonable uses;

(5) Maintain, protect, and enhance the quality of the human environment;

(6) Ensure visibility of all mooring cables; and

(7) Comply with § 1304.205(c).

(d) Electrical. Floating cabins shall comply with all applicable federal, state, and local laws and regulations regarding electrical wiring and equipment. If a floating cabin is documented to be in violation of any federal, state, or local electrical standard or regulation by the respective regulatory agency, TVA is authorized to revoke the permit and require removal of the floating cabin from the Tennessee River System if the violation is not corrected as specified by the regulatory agency in accordance with the agency's requirements. Floating cabins shall comply with § 1304.209(c)(2).

(e) Electrical certifications. Floating cabin owners shall provide, in a form acceptable to TVA, certification of compliance with the electrical standards of paragraphs (e)(1) and (2) of this section with their initial permit application, no later than October 1, 2024, and by October 1 of every even-numbered year thereafter. The certification must be signed by a licensed electrical engineer, a state-certified electrical inspector, or a person certified by the International Association of Electrical Inspectors, the International Code Council, or an equivalent organization.

(1) All floating cabins must meet the following minimum requirements for ground fault protection:

(i) The feeder(s) from electrical service on the shore to the floating cabin shall have ground fault protection not exceeding 100 milliamps.

(ii) If the floating cabin has a transformer, the transformer shall have ground fault protection not exceeding 100 milliamps at the first overcurrent protection device on the secondary side of the transformer. The conductors from the transformer enclosure to the overcurrent protection device shall not exceed ten feet and shall be installed in a raceway.

(iii) If the floating cabin is located in a marina and the feeder supplying the floating cabin is part of the marina's electrical system, the feeder shall have ground fault protection not exceeding 100 milliamps.

(iv) If another source of electrical power is utilized on a floating cabin, such as but not limited to a generator, photovoltaic cell, or wind turbine, the source of electrical power shall have ground fault protection not exceeding 100 milliamps at the first overcurrent protection device for each source. For permanently installed sources, the conductors from the source to the first overcurrent protection device shall not exceed ten feet and shall be installed in a raceway.

(v) The floating cabin owner may determine the devices that are utilized to achieve the ground fault protection requirement provided such devices are labeled and listed from a third-party testing laboratory for the purpose of the installation.

(2) If power is supplied to the floating cabin by an underwater cable, the portable power cable shall, at a minimum, meet the requirements of National Fire Protection Association 70 Article 555.13 (A)(2) and (B)(4) of the 2017 National Electrical Code. For new portable power cables installed after October 12, 2021, the cables shall meet the requirements of the most recent version of the National Electric Code.

[86 FR 50635, Sept. 10, 2021]