Regulations last checked for updates: Nov 25, 2024
Title 30 - Mineral Resources last revised: Nov 19, 2024
§ 56.12001 - Circuit overload protection.
Circuits shall be protected against excessive overload by fuses or circuit breakers of the correct type and capacity.
§ 56.12002 - Controls and switches.
Electric equipment and circuits shall be provided with switches or other controls. Such switches or controls shall be of approved design and construction and shall be properly installed.
§ 56.12003 - Trailing cable overload protection.
Individual overload protection or short circuit protection shall be provided for the trailing cables of mobile equipment.
§ 56.12004 - Electrical conductors.
Electrical conductors shall be of a sufficient size and current-carrying capacity to ensure that a rise in temperature resulting from normal operations will not damage the insulating materials. Electrical conductors exposed to mechanical damage shall be protected.
§ 56.12005 - Protection of power conductors from mobile equipment.
Mobile equipment shall not run over power conductors, nor shall loads be dragged over power conductors, unless the conductors are properly bridged or protected.
§ 56.12006 - Distribution boxes.
Distribution boxes shall be provided with a disconnecting device for each branch circuit. Such disconnecting devices shall be equipped or designed in such a manner that it can be determined by visual observation when such a device is open and that the circuit is deenergized, the distribution box shall be labeled to show which circuit each device controls.
§ 56.12007 - Junction box connection procedures.
Trailing cable and power-cable connections to junction boxes shall not be made or broken under load.
§ 56.12008 - Insulation and fittings for power wires and cables.
Power wires and cables shall be insulated adequately where they pass into or out of electrical compartments. Cables shall enter metal frames of motors, splice boxes, and electrical compartments only through proper fittings. When insulated wires, other than cables, pass through metal frames, the holes shall be substantially bushed with insulated bushings.
§ 56.12010 - Isolation or insulation of communication conductors.
Telephone and low-potential signal wire shall be protected, by isolation or suitable insulation, or both, from contacting energized power conductors or any other power source.
§ 56.12011 - High-potential electrical conductors.
High-potential electrical conductors shall be covered, insulated, or placed to prevent contact with low potential conductors.
§ 56.12012 - Bare signal wires.
The potential on bare signal wires accessible to contact by persons shall not exceed 48 volts.
§ 56.12013 - Splices and repairs of power cables.
Permanent splices and repairs made in power cables, including the ground conductor where provided, shall be:
(a) Mechanically strong with electrical conductivity as near as possible to that of the original;
(b) Insulated to a degree at least equal to that of the original, and sealed to exclude moisture; and
(c) Provided with damage protection as near as possible to that of the original, including good bonding to the outer jacket.
§ 56.12014 - Handling energized power cables.
Power cables energized to potentials in excess of 150 volts, phase-to-ground, shall not be moved with equipment unless sleds or slings, insulated from such equipment, are used. When such energized cables are moved manually, insulated hooks, tongs, ropes, or slings shall be used unless suitable protection for persons is provided by other means. This does not prohibit pulling or dragging of cable by the equipment it powers when the cable is physically attached to the equipment by suitable mechanical devices, and the cable is insulated from the equipment in conformance with other standards in this part.
§ 56.12016 - Work on electrically-powered equipment.
Electrically powered equipment shall be deenergized before mechanical work is done on such equipment. Power switches shall be locked out or other measures taken which shall prevent the equipment from being energized without the knowledge of the individuals working on it. Suitable warning notices shall be posted at the power switch and signed by the individuals who are to do the work. Such locks or preventive devices shall be removed only by the persons who installed them or by authorized personnel.
§ 56.12017 - Work on power circuits.
Power circuits shall be deenergized before work is done on such circuits unless hot-line tools are used. Suitable warning signs shall be posted by the individuals who are to do the work. Switches shall be locked out or other measures taken which shall prevent the power circuits from being energized without the knowledge of the individuals working on them. Such locks, signs, or preventative devices shall be removed only by the person who installed them or by authorized personnel.
§ 56.12018 - Identification of power switches.
Principal power switches shall be labeled to show which units they control, unless identification can be made readily by location.
§ 56.12019 - Access to stationary electrical equipment or switchgear.
Where access is necessary, suitable clearance shall be provided at stationary electrical equipment or switchgear.
§ 56.12020 - Protection of persons at switchgear.
Dry wooden platforms, insulating mats, or other electrically nonconductive material shall be kept in place at all switchboards and power-control switches where shock hazards exist. However, metal plates on which a person normally would stand and which are kept at the same potential as the grounded, metal, non-current-carrying parts of the power switches to be operated may be used.
§ 56.12021 - Danger signs.
Suitable danger signs shall be posted at all major electrical installations.
§ 56.12022 - Authorized persons at major electrical installations.
Areas containing major electrical installations shall be entered only by authorized persons.
§ 56.12023 - Guarding electrical connections and resistor grids.
Electrical connections and resistor grids that are difficult or impractical to insulate shall be guarded, unless protection is provided by location.
§ 56.12025 - Grounding circuit enclosures.
All metal enclosing or encasing electrical circuits shall be grounded or provided with equivalent protection. This requirement does not apply to battery-operated equipment.
§ 56.12026 - Grounding transformer and switchgear enclosures.
Metal fencing and metal buildings enclosing transformers and switchgear shall be grounded.
§ 56.12027 - Grounding mobile equipment.
Frame grounding or equivalent protection shall be provided for mobile equipment powered through trailing cables.
§ 56.12028 - Testing grounding systems.
Continuity and resistance of grounding systems shall be tested immediately after installation, repair, and modification; and annually thereafter. A record of the resistance measured during the most recent tests shall be made available on a request by the Secretary or his duly authorized representative.
§ 56.12030 - Correction of dangerous conditions.
When a potentially dangerous condition is found it shall be corrected before equipment or wiring is energized.
§ 56.12032 - Inspection and cover plates.
Inspection and cover plates on electrical equipment and junction boxes shall be kept in place at all times except during testing or repairs.
§ 56.12033 - Hand-held electric tools.
Hand-held electric tools shall not be operated at high potential voltages.
§ 56.12034 - Guarding around lights.
Portable extension lights, and other lights that by their location present a shock or burn hazard, shall be guarded.
§ 56.12035 - Weatherproof lamp sockets.
Lamp sockets shall be of a weatherproof type where they are exposed to weather or wet conditions that may interfere with illumination or create a shock hazard.
§ 56.12036 - Fuse removal or replacement.
Fuses shall not be removed or replaced by hand in an energized circuit, and they shall not otherwise be removed or replaced in an energized circuit unless equipment and techniques especially designed to prevent electrical shock are provided and used for such purpose.
§ 56.12037 - Fuses in high-potential circuits.
Fuse tongs or hot line tools shall be used when fuses are removed or replaced in high-potential circuits.
§ 56.12038 - Attachment of trailing cables.
Trailing cables shall be attached to machines in a suitable manner to protect the cable from damage and to prevent strain on the electrical connections.
§ 56.12039 - Protection of surplus trailing cables.
Surplus trailing cables to shovels, cranes and similar equipment shall be—
(a) Stored in cable boats;
(b) Stored on reels mounted on the equipment; or
(c) Otherwise protected from mechanical damage.
§ 56.12040 - Installation of operating controls.
Operating controls shall be installed so that they can be operated without danger of contact with energized conductors.
§ 56.12041 - Design of switches and starting boxes.
Switches and starting boxes shall be of safe design and capacity.
§ 56.12042 - Track bonding.
Both rails shall be bonded or welded at every joint and rails shall be crossbonded at least every 200 feet if the track serves as the return trolley circuit. When rails are moved, replaced, or broken bonds are discovered, they shall be rebonded within three working shifts.
§ 56.12045 - Overhead powerlines.
Overhead high-potential powerlines shall be installed as specified by the National Electrical Code.
§ 56.12047 - Guy wires.
Guy wires of poles supporting high-voltage transmission lines shall meet the requirements for grounding or insulator protection of the National Electrical Safety Code, part 2, entitled “Safety Rules for the Installation and Maintenance of Electric Supply and Communication Lines” (also referred to as National Bureau of Standards Handbook 81, November 1, 1961) and Supplement 2 thereof issued March 1968, which are hereby incorporated by reference and made a part hereof. These publications and documents may be obtained from the National Institute of Science and Technology, 100 Bureau Drive, Stop 3460, Gaithersburg, MD 20899-3460. Telephone: 301-975-6478 (not a toll free number); http://ts.nist.gov/nvl; or from the Government Printing Office, Information Dissemination (Superintendent of Documents), P.O. Box 371954, Pittsburgh, PA 15250-7954; Telephone: 866-512-1800 (toll free) or 202-512-1800, http://bookstore.gpo.gov, or may be examined in any Metal and Nonmetal Mine Safety and Health District Office of the Mine Safety and Health Administration.
[50 FR 4054, Jan. 29, 1985, as amended at 60 FR 35695, July 11, 1995; 71 FR 16667, Apr. 3, 2006]
§ 56.12048 - Communication conductors on power poles.
Telegraph, telephone, or signal wires shall not be installed on the same crossarm with power conductors. When carried on poles supporting powerlines, they shall be installed as specified by the National Electrical Code.
§ 56.12050 - Installation of trolley wires.
Trolley wires shall be installed at least seven feet above rails where height permits, and aligned and supported to suitably control sway and sag.
§ 56.12053 - Circuits powered from trolley wires.
Ground wires for lighting circuits powered from trolley wires shall be connected securely to the ground-return circuit.
§ 56.12065 - Short circuit and lightning protection.
Powerlines, including trolley wires, and telephone circuits shall be protected against short circuits and lightning.
§ 56.12066 - Guarding trolley wires and bare powerlines.
Where metallic tools or equipment can come in contact with trolley wires or bare powerlines, the lines shall be guarded or deenergized.
§ 56.12067 - Installation of transformers.
Transformers shall be totally enclosed, or shall be placed at least 8 feet above the ground, or installed in a transformer house, or surrounded by a substantial fence at least 6 feet high and at least 3 feet from any energized parts, casings, or wiring.
§ 56.12068 - Locking transformer enclosures.
Transformer enclosures shall be kept locked against unauthorized entry.
§ 56.12069 - Lightning protection for telephone wires and ungrounded conductors.
Each ungrounded power conductor or telephone wire that leads underground and is directly exposed to lightning shall be equipped with suitable lightning arrestors of approved type within 100 feet of the point where the circuit enters the mine. Lightning arrestors shall be connected to a low resistance grounding medium on the surface and shall be separated from neutral grounds by a distance of not less than 25 feet.
§ 56.12071 - Movement or operation of equipment near high-voltage power lines.
When equipment must be moved or operated near energized high-voltage powerlines (other than trolley lines) and the clearance is less than 10 feet, the lines shall be deenergized or other precautionary measures shall be taken.
source: 50 FR 4054, Jan. 29, 1985, unless otherwise noted.
cite as: 30 CFR 56.12005