Regulations last checked for updates: Nov 25, 2024

Title 46 - Shipping last revised: Nov 04, 2024
§ 64.57 - Acceptance of pressure relief devices.

A pressure relief device for an MPT must be—

(a) From a supplier accepted under chapter I of title 46, Code of Federal Regulations; or

Note 1 to paragraph (a):

Accepted suppliers are listed in CG-190, Equipment list.

(b) Accepted by the Coast Guard in accordance with the procedures in § 50.25-10 of this subchapter.

[CGD 84-043, 55 FR 37410, Sept. 11, 1990, as amended by USCG-2020-0634, 89 FR 50199, June 12, 2024]
§ 64.59 - Spring loaded pressure relief valve.

A spring loaded pressure relief valve must—

(a) Be set at a nominal pressure of 125 percent of the maximum allowable working pressure;

(b) Have a minimum normal venting capacity that is sufficient to prevent the tank pressure from exceeding 137.5 percent of the maximum allowable working pressure;

(c) Close after discharge of a pressure not lower than 115 percent of the maximum allowable working pressure; and

(d) If closed, remain closed at any pressure less than 115 percent of the maximum allowable working pressure.

§ 64.61 - Rupture disc.

If a rupture disc is the only pressure relief device on the tank, the rupture disc must—

(a) Rupture at a pressure of 125 percent of the maximum allowable working pressure; and

(b) Have a minimum normal venting capacity that is sufficient to prevent the tank pressure from exceeding 137.5 percent of the maximum allowable working pressure.

§ 64.63 - Minimum emergency venting capacity.

(a) The total emergency venting capacity (Q) of the relief devices of an uninsulated MPT must be in accordance with table 1 to § 64.63 or the following formula based upon the pressure relief device operating at a pressure not to exceed the test pressure:

Formula 1 to Paragraph (a) Where: Q = Minimum required rate of discharge in cubic feet per minute of free air at standard conditions (60 °F and 14.7 psia). M = Molecular weight of the product, or 86.7. T = Temperature, degrees Rankine (460° + temperature in °F of gas at relieving temperature), or 710 °R. A = Total external surface area of the tank compartment in square feet. L = Latent heat of the product being vaporized at relieving conditions in Btu per pound, or 144 Btu per pound. Z = Compressibility factor of the gas at relieving conditions, or 1.0. C = Constant based on relation of specific heats, equal to 315.

(b) The total emergency venting capacity (Q) of an insulated portable tank may have a reduction if—

(1) It is shown to the Coast Guard that the insulation reduces the heat transmission to the tank;

(2) The present reduction of the emergency venting capacity (Q) is limited to the percent reduction of the heat transmission to the tank or 50 percent, whichever is less; and

(3) The insulation is sheathed.

Table 1 to § 64.63—Minimum Emergency Venting Capacity in Cubic Feet: Free Air/Hour

[14.7 lb/in 2a and 60 °F]

Exposed area
square feet 1
Cubic feet free air
per hour
Exposed area
square feet 1
Cubic feet free air
per hour
2027,600275237,000
3038,500300256,000
4048,600350289,500
5058,600400322,100
6067,700450355,900
7077,000500391,000
8085,500550417,500
9094,800600450,000
100104,000650479,000
120121,000700512,000
140136,200750540,000
160152,100800569,000
180168,200850597,000
200184,000900621,000
225199,000950656,000
250219,5001,000685,000

1 Interpolate for intermediate sizes.

[CGD 73-172, 39 FR 22950, June 25, 1974, as amended by CGD 84-043, 55 FR 37410, Sept. 11, 1990; 55 FR 47477, Nov. 14, 1990; USCG-2020-0634, 89 FR 50199, June 12, 2024]
§ 64.65 - Vacuum relief device.

(a) Each MPT that is designed for an external pressure of less than 7.5 psig must have a vacuum relief device.

(b) A vacuum relief device for an MPT must—

(1) Open at an external pressure of not less than 3 psig; and

(2) Have an opening with a cross-section of 0.44 square inch or more.

[CGD 84-043, 55 FR 37410, Sept. 11, 1990]
§ 64.67 - Shutoff valve.

A shutoff valve may not be located—

(a) Between the tank opening and pressure relief device; or

(b) On the discharge side of the pressure relief device.

§ 64.69 - Location of the pressure relief device.

A pressure relief device must be—

(a) Accessible for inspection and repair before stowage of the tank; and

(b) Attached so that escaping gas does not impinge on the tank or framework.

§ 64.71 - Marking of pressure relief devices.

A pressure relief device must be plainly and permanently marked with the—

(a) Set pressure rating;

(b) Rated flow capacity expressed as cubic feet of standard air (60 °F 14.7 psia) per minute and the pressure at which the flow capacity is determined;

(c) Manufacturer's name and identifying number; and

(d) Pipe size of inlet.

authority: 46 U.S.C. 3306,3703; 49 U.S.C. App. 1804; Department of Homeland Security Delegation No. 00170.1, Revision No. 01.3
source: CGD 73-172, 39 FR 22950, June 25, 1974, unless otherwise noted.
cite as: 46 CFR 64.67