Regulations last checked for updates: Nov 22, 2024
Title 46 - Shipping last revised: Nov 04, 2024
§ 193.50-1 - Application.
(a) The provisions of this subpart, with the exception of § 193.50-90, apply to all vessels, including non-self-propelled vessels of less than 300 gross tons, contracted for on or after March 1, 1968.
(b) All vessels other than unmanned barges contracted for prior to March 1, 1968, must meet the requirements of § 193.50-90.
(c) All unmanned barges are exempted from the requirements in this subpart. However, if such barges carry on board hand portable fire extinguishers and semi-portable fire extinguishing systems, then such equipment must be in accordance with this subpart for manned barges.
[CGFR 67-83, 33 FR 1145, Jan. 27, 1968, as amended by USCG-2012-0196, 81 FR 48301, July 22, 2016]
§ 193.50-10 - Location.
(a) Approved portable fire extinguishers and semi-portable fire extinguishing systems must be installed in accordance with Table 193.50-10(a) of this section. The location of the equipment must be to the satisfaction of the Officer in Charge, Marine Inspection (OCMI). Nothing in this paragraph must be construed as limiting the OCMI from requiring such additional equipment as he or she deems necessary for the proper protection of the vessel.
(b) Table 193.50-10(a) indicates the minimum required classification for each space listed. Extinguishers with larger numerical ratings or multiple letter designations may be used if the extinguishers meet the requirements of the table.
(c) Semi-portable fire extinguishing systems must be located in the open so as to be readily seen.
(d) If portable fire extinguishers are not located in the open or behind glass so that they may be readily seen, they may be placed in enclosures together with the firehose, provided such enclosures are marked as required by § 196.37-15 of this subchapter.
Table 193.50-10(a)—Carriage of Portable Fire Extinguisher and Semi-Portable Fire Extinguishing Systems
Space
| Minimum required rating
| Quantity and location
|
---|
Safety Areas
|
Wheelhouse or fire control room | | None.
|
Stairway and elevator enclosures | | None.
|
Communicating corridors | 2-A | 1 in each main corridor not more than 150 ft apart. (May be located in stairways.)
|
Lifeboat embarkation and lowering stations | | None.
|
Radio room | 20-B:C
1 | 2 in the vicinity of the exit.
1
|
Accommodations
|
Staterooms, toilet spaces, public spaces, offices, lockers, isolated storerooms, pantries, open decks, etc | | None.
|
Service Spaces
|
Galleys | 40-B:C | 1 for each 2,500 sq ft or fraction thereof.
|
Machinery Spaces
|
Paint and lamp rooms | 40-B | 1 outside space in the vicinity of the exit.
|
Accessible baggage, mail, and specie rooms, and storerooms | 2-A | 1 for each 2,500 sq ft or fraction thereof located in the vicinity of the exits, either inside or outside the spaces.
|
Carpenter shop and similar spaces | 2-A | 1 outside the space in the vicinity of the exit.
|
Coal-fired boilers: Bunker and boiler space | | None.
|
Oil-fired boilers: Spaces containing oil-fired boilers, either main or auxiliary, or their fuel-oil units | 40-B | 2 required.
2
|
| 160-B | 1 required.
3
|
Internal combustion or gas turbine propelling machinery spaces | 40-B | 1 for each 1,000 brake horsepower, but not fewer than 2 nor more than 6.
4
|
| 120-B | 1 required.
5 6
|
Electric propulsive motors or generators of open type | 40-B:C | 1 for each propulsion motor or generator unit.
|
Enclosed ventilating systems for motors and generators of electric propelling machinery | | None.
|
Auxiliary Spaces
|
Internal combustion gas turbine | 40-B | 1 outside the space in vicinity of the exit.
6
|
Electric emergency motors or generators | 40-B:C | 1 outside the space in vicinity of the exit.
7
|
Steam | | None required.
|
Trunks to machinery spaces | | None required.
|
Fuel tanks | | None required.
|
Scientific Spaces
|
Chemistry laboratory or scientific laboratory | 40-B:C | 2 for each 300 sq ft of deck space or fraction thereof, with one (1) of each kind located in the vicinity of the exit.
|
Chemical storeroom | 40-B:C | Same as for the chemistry laboratory.
|
Spare Units
|
| 2-A | 10 percent of required units rounded up.
|
| 40-B:C | 10 percent of required units rounded up.
|
(e) Portable fire extinguishers and their stations must be numbered in accordance with § 196.37-15 of this subchapter.
(f) Portable or semi-portable extinguishers, which are required on their nameplates to be protected from freezing, must not be located where freezing temperatures may be expected.
[USCG-2012-0196, 81 FR 48302, July 22, 2016]
§ 193.50-20 - Semi-portable fire extinguishers.
(a) The frame or support of each semi-portable fire extinguisher required by Table 193.50-10(a) of this subpart must be welded or otherwise permanently attached to a bulkhead or deck.
(b) If an approved semi-portable fire extinguisher has wheels and is not required by Table 193.50-10(a) of this subpart, it must be securely stowed when not in use to prevent it from rolling out of control under heavy sea conditions.
(c) Semi-portable extinguishers must be fitted with suitable hose and nozzle, or other practicable means, so that all areas of the space can be protected.
[CGD 77-039, 44 FR 34133, June 14, 1979, as amended by USCG-2012-0196, 81 FR 48304, July 22, 2016]
§ 193.50-80 - Locations and number of fire extinguishers required for vessels constructed prior to August 22, 2016.
Vessels contracted for prior to August 22, 2016, must meet the following requirements:
(a) Previously installed extinguishers with extinguishing capacities smaller than what is required in Table 193.50-10(a) of this subpart need not be replaced and may be continued in service so long as they are maintained in good condition to the satisfaction of the Officer in Charge, Marine Inspection.
(b) All new equipment and installations must meet the applicable requirements in this subpart for new vessels.
[USCG-2012-0196, 81 FR 48304, July 22, 2016]
§ 193.50-90 - Vessels contracted for prior to March 1, 1968.
(a) Vessels contracted for prior to March 1, 1968, must meet the following requirements:
(1) Except as specifically modified by this paragraph, the requirements of § 193.50-10 must be complied with insofar as the number and general type of equipment is concerned.
(2) Existing installations previously approved, but not meeting the applicable requirements of § 193.50-10, may be continued in service so long as they are maintained in good condition to the satisfaction of the Officer in Charge, Marine Inspection, and they are in general agreement with the degree of safety prescribed by Table 193.50-10(a) of this subpart. Minor modifications may be made to the same standard as the original installation, provided that in no case will a greater departure from the standards of Table 193.50-10(a) of this subpart be permitted than presently exists.
(3) All new equipment and installations must meet the applicable requirements in this subpart for new vessels.
[USCG-2012-0196, 81 FR 48304, July 22, 2016]
authority: 46 U.S.C. 2213,
3102,
3306; E.O. 12234, 45 FR 58801, 3 CFR, 1980 Comp., p. 277; Department of Homeland Security Delegation No. 0170.1
source: CGFR 67-83, 33 FR 1145, Jan. 27, 1968, unless otherwise noted.
cite as: 46 CFR 193.50-20