(a) Scope. This section provides test procedures, pursuant to the Energy Policy and Conservation Act (EPCA), as amended, which must be followed for measuring the combustion efficiency and/or thermal efficiency of a gas- or oil-fired commercial packaged boiler.
(b) Testing and Calculations. Determine the thermal efficiency or combustion efficiency of commercial packaged boilers by conducting the appropriate test procedure(s) indicated in Table 1 of this section.
Table 1—Test Requirements for Commercial Packaged Boiler Equipment Classes
Equipment category
| Subcategory
| Certified rated input
Btu/h
| Standards efficiency metric
(§ 431.87)
| Test procedure
(corresponding to
standards efficiency
metric required
by § 431.87)
|
---|
Hot Water | Gas-fired | ≥300,000 and ≤2,500,000 | Thermal Efficiency | Appendix A, Section 2.
|
Hot Water | Gas-fired | >2,500,000 | Combustion Efficiency | Appendix A, Section 3.
|
Hot Water | Oil-fired | ≥300,000 and ≤2,500,000 | Thermal Efficiency | Appendix A, Section 2.
|
Hot Water | Oil-fired | >2,500,000 | Combustion Efficiency | Appendix A, Section 3.
|
Steam | Gas-fired (all*) | ≥300,000 and ≤2,500,000 | Thermal Efficiency | Appendix A, Section 2.
|
Steam | Gas-fired (all*) | >2,500,000 and ≤5,000,000 | Thermal Efficiency | Appendix A, Section 2.
|
| | >5,000,000 | Thermal Efficiency | Appendix A, Section 2.
OR
Appendix A, Section 3 with Section 2.4.3.2.
|
Steam | Oil-fired | ≥300,000 and ≤2,500,000 | Thermal Efficiency | Appendix A, Section 2.
|
Steam | Oil-fired | >2,500,000 and ≤5,000,000 | Thermal Efficiency | Appendix A, Section 2.
|
| | >5,000,000 | Thermal Efficiency | Appendix A, Section 2.
OR
Appendix A, Section 3. with Section 2.4.3.2.
|
(c) Field Tests. The field test provisions of appendix A may be used only to test a unit of commercial packaged boiler with rated input greater than 5,000,000 Btu/h.
[81 FR 89305, Dec. 9, 2016]