§ 64.93 - Pump controls.

(a) A pressure gauge must be installed—

(1) On the pump discharge;

(2) Near the pump controls; and

(3) Visible to the operator.

(b) A pump must have a remote, quick acting, manual shutdown that is conspicuously labeled and located in an easily accessible area away from the pump. The quick acting, manual shutdown for remote operation must provide a means of stopping the pump power unit.

authority: 46 U.S.C. 3306,3703; 49 U.S.C. App. 1804; Department of Homeland Security Delegation No. 00170.1, Revision No. 01.3
source: CGD 73-172, 39 FR 22950, June 25, 1974, unless otherwise noted.
cite as: 46 CFR 64.93