§ 108.411 - Smoke detection system.

Each smoke accumulator in a smoke detection system must be located on the overhead of the compartment protected by the system in a location—

(a) Where no portion of the overhead of the compartment is more than 12 meters (40 feet) from an accumulator;

(b) That is no closer to the opening of a ventilator than 3 times the diameter or equivalent size of the opening.

(c) Where damage to the accumulator is unlikely to occur if it is not protected.

authority: 43 U.S.C. 1333; 46 U.S.C. 3102,3306; Department of Homeland Security Delegation No. 0170.1
source: CGD 73-251, 43 FR 56808, Dec. 4, 1978, unless otherwise noted.
cite as: 46 CFR 108.411