Regulations last checked for updates: Oct 18, 2024

Title 46 - Shipping last revised: Oct 15, 2024
§ 108.469 - Quantity of foam producing materials.

(a) Except as provided in paragraph (b) of this section, each foam extinguishing system with outlets—

(1) In a tank must have enough foam producing material to discharge foam for at least 5 minutes at each outlet; and

(2) In a space must have enough foam producing material to discharge foam for at least 3 minutes at each outlet.

(b) If a foam system has outlets in more than one tank or space, the system need have only enough foam producing material to cover the largest space that the system covers or, if the liquid surface of a tank covered by the system is larger, the tank with the largest liquid surface.

authority: 43 U.S.C. 1333; 46 U.S.C. 3102,3306; Department of Homeland Security Delegation No. 0170.1
source: CGD 73-251, 43 FR 56808, Dec. 4, 1978, unless otherwise noted.
cite as: 46 CFR 108.469