The coverage of each dry chemical system monitor under § 154.1150 must not exceed:
(a) 10 m (32.8 ft.) at 10 kg/sec (22 lb/sec);
(b) 30 m (98.4 ft.) at 25 kg/sec (55 lb/sec);
(c) 40 m (131.2 ft.) at 45 kg/sec (99 lb/sec);
(d) An interpolation between 10 m (32.8 ft.) at 10 kg/sec (22 lb/sec) and 30 m (98.4 ft.) at 25 kg/sec (55 lb/sec); or
(e) An interpolation between 30 m (98.4 ft.) at 25 kg/sec (55 lb/sec) and 40 m (131.2 ft.) at 45 kg/sec (99 lb/sec).
source: CGD 74-289, 44 FR 26009, May 3, 1979, unless otherwise noted.
cite as: 46 CFR 154.1160