Except for definite purpose motors, special purpose motors, and those motors exempted by the Secretary under paragraph (2),
2
See References in Text note below.
each electric motor manufactured (alone or as a component of another piece of equipment) after the 60-month period beginning on
October 24, 1992, or in the case of an electric motor which requires listing or certification by a nationally recognized safety testing laboratory, after the 84-month period beginning on
October 24, 1992, shall have a nominal full load efficiency of not less than the following:
Number of poles | Nominal Full-Load Efficiency |
---|
Open Motors | Closed Motors |
---|
6 | 4 | 2 | 6 | 4 | 2 |
---|
Motor Horsepower | | | | | | |
1 | 80.0 | 82.5 | ....... | 80.0 | 82.5 | 75.5 |
1.5 | 84.0 | 84.0 | 82.5 | 85.5 | 84.0 | 82.5 |
2 | 85.5 | 84.0 | 84.0 | 86.5 | 84.0 | 84.0 |
3 | 86.5 | 86.5 | 84.0 | 87.5 | 87.5 | 85.5 |
5 | 87.5 | 87.5 | 85.5 | 87.5 | 87.5 | 87.5 |
7.5 | 88.5 | 88.5 | 87.5 | 89.5 | 89.5 | 88.5 |
10 | 90.2 | 89.5 | 88.5 | 89.5 | 89.5 | 89.5 |
15 | 90.2 | 91.0 | 89.5 | 90.2 | 91.0 | 90.2 |
20 | 91.0 | 91.0 | 90.2 | 90.2 | 91.0 | 90.2 |
25 | 91.7 | 91.7 | 91.0 | 91.7 | 92.4 | 91.0 |
30 | 92.4 | 92.4 | 91.0 | 91.7 | 92.4 | 91.0 |
40 | 93.0 | 93.0 | 91.7 | 93.0 | 93.0 | 91.7 |
50 | 93.0 | 93.0 | 92.4 | 93.0 | 93.0 | 92.4 |
60 | 93.6 | 93.6 | 93.0 | 93.6 | 93.6 | 93.0 |
75 | 93.6 | 94.1 | 93.0 | 93.6 | 94.1 | 93.0 |
100 | 94.1 | 94.1 | 93.0 | 94.1 | 94.5 | 93.6 |
125 | 94.1 | 94.5 | 93.6 | 94.1 | 94.5 | 94.5 |
150 | 94.5 | 95.0 | 93.6 | 95.0 | 95.0 | 94.5 |
|