Regulations last checked for updates: Nov 24, 2024

Title 10 - Energy last revised: Nov 19, 2024
§ 460.204 - Mechanical ventilation fan efficacy.

(a) Whole-house mechanical ventilation system fans must meet the minimum efficacy requirements set forth in table 1 to 460.204(a), except as provided in paragraph (b) of this section. The mechanical ventilation fan efficacy requirements are adapted from section R403 of the 2021 IECC.

Table 1 to § 460.204(a)—Mechanical Ventilation System Fan Efficacy

Fan type description Airflow rate
minimum
(cfm)
Minimum
efficacy
(cfm/watt)
Heat recovery ventilator or energy recovery ventilatorAny1.2
In-line supply or exhaust fansAny3.8
Other exhaust fan<902.8
Other exhaust fan≥903.5

(b) Mechanical ventilation fans that are integral to heating, ventilating, and air conditioning equipment, including furnace fans as defined in § 430.2 of this subchapter, are not subject to the efficiency requirements in paragraph (a) of this section.

source: 87 FR 32818, May 31, 2022, unless otherwise noted.
cite as: 10 CFR 460.204