Generator, feeder, and bus-tie cables must be selected on the basis of a computed load of not less than the demand load given in Table 111.60-7.
Type of circuit
| Demand load
|
---|
Generator Cables | 115 percent of continuous generator rating.
|
Switchboard bus-ties, except ship's service to emergency switchboard bus-ties | 75 percent of generating capacity of the larger switchboard.
|
Emergency switchboard bus-ties | 115 percent of continuous rating of emergency generator.
|
Motor feeders | Article 430 of NFPA 70 (incorporated by reference; see § 110.10-1 of this subchapter).
|
Galley equipment feeders | 100 percent of either the first 50 kW or one-half the connected load, whichever is the larger, plus 65 percent of the remaining connected load, plus 50 percent of the rating of the spare switches or circuit breakers on the distribution panel.
|
Lighting feeders | 100 percent of the connected load plus the average active circuit load for the spare switches or circuit breakers on the distribution panels.
|
Grounded neutral of a dual voltage feeders | 100 percent of the capacity of the ungrounded conductors when grounded neutral is not protected by a circuit breaker overcurrent trip, or not less than 50 percent of the capacity of the ungrounded conductors when the grounded neutral is protected by a circuit breaker overcurrent trip or overcurrent alarm. |
[CGD 74-125A, 47 FR 15236, Apr. 8, 1982, as amended by USCG-2004-18884, 69 FR 58348, Sept. 30, 2004; USCG-2003-16630, 73 FR 65198, Oct. 31, 2008; USCG-2020-0075, 88 FR 16364, Mar. 16, 2023]
authority: 46 U.S.C. 3306,
3703; DHS Delegation No. 00170.1, Revision No. 01.2. Section 111.05-20 and Subpart 111.106 also issued under sec. 617, Pub. L. 111-281, 124 Stat. 2905
source: CGD 74-125A, 47 FR 15236, Apr. 8, 1982, unless otherwise noted.
cite as: 46 CFR 111.60-7