Except as provided in § 445.1, this subpart applies to discharges of wastewater from landfills subject to the provisions of 40 CFR part 258, Criteria for Municipal Solid Waste Landfills; and 40 CFR part 257, Criteria for Classification of Solid Waste Disposal Facilities and Practices.
Except as provided in 40 CFR 125.30 through 125.32, any existing point source subject to this subpart must achieve the following effluent limitations which represent the application of BPT:
Regulated parameter
| Maximum daily
1
| Maximum monthly avg.
1
|
---|
BOD | 140 | 37
|
TSS | 88 | 27
|
Ammonia (as N) | 10 | 4.9
|
α-Terpineol | 0.033 | 0.016
|
Benzoic acid | 0.12 | 0.071
|
p-Cresol | 0.025 | 0.014
|
Phenol | 0.026 | 0.015
|
Zinc | 0.20 | 0.11
|
pH | (
2) | (
2)
|
[65 FR 3048, Jan. 19, 2000; 65 FR 14344, Mar. 16, 2000]
Except as provided in 40 CFR 125.30 through 125.32, any existing point source subject to this subpart must achieve the following effluent limitations which represent the application of BCT: Limitations for BOD5, TSS and pH are the same as the corresponding limitations specified in § 445.21.
Except as provided in 40 CFR 125.30-125.32, any existing point source subject to this subpart must achieve the following effluent limitations which represent the application of BAT: Limitations for ammonia (as N), a-terpineol, benzoic acid, p-cresol, phenol and zinc are the same as the corresponding limitations specified in § 445.21.
Any new source subject to this subpart must achieve the following performance standards: Standards are the same as those specified in § 445.21.
authority: Secs. 301, 304, 306, 307, 308, 402 and 501 of the Clean Water Act, as amended (
33 U.S.C. 1311,
1314,
1316,
1317,
1318,
1342
source: 65 FR 3048, Jan. 19, 2000, unless otherwise noted.
cite as: 40 CFR 445.23