Appendix - Table 1 to Subpart JJJJJJ of Part 63—Emission Limits

As stated in § 63.11201, you must comply with the following applicable emission limits:

If your boiler is in this subcategory . . . For the following
pollutants . . .
You must achieve less than or equal to the following emission limits, except during periods of startup and shutdown . . .
1. New coal-fired boilers with heat input capacity of 30 million British thermal units per hour (MMBtu/hr) or greater that do not meet the definition of limited-use boilera. PM (Filterable)
b. Mercury
c. CO
3.0E-02 pounds(lb) per million British thermal units (MMBtu) of heat input.
2.2E-05 lb per MMBtu of heat input.
420 parts per million (ppm) by volume on a dry basis corrected to 3 percent oxygen (3-run average or 10-day rolling average).
2. New coal-fired boilers with heat input capacity of between 10 and 30 MMBtu/hr that do not meet the definition of limited-use boilera. PM (Filterable)
b. Mercury
c. CO
4.2E-01 lb per MMBtu of heat input.
2.2E-05 lb per MMBtu of heat input.
420 ppm by volume on a dry basis corrected to 3 percent oxygen (3-run average or 10-day rolling average).
3. New biomass-fired boilers with heat input capacity of 30 MMBtu/hr or greater that do not meet the definition of seasonal boiler or limited-use boilerPM (Filterable)3.0E-02 lb per MMBtu of heat input.
4. New biomass fired boilers with heat input capacity of between 10 and 30 MMBtu/hr that do not meet the definition of seasonal boiler or limited-use boilerPM (Filterable)7.0E-02 lb per MMBtu of heat input.
5. New oil-fired boilers with heat input capacity of 10 MMBtu/hr or greater that do not meet the definition of seasonal boiler or limited-use boilerPM (Filterable)3.0E-02 lb per MMBtu of heat input.
6. Existing coal-fired boilers with heat input capacity of 10 MMBtu/hr or greater that do not meet the definition of limited-use boilera. Mercury
b. CO
2.2E-05 lb per MMBtu of heat input.
420 ppm by volume on a dry basis corrected to 3 percent oxygen (3-run average or 10-day rolling average).
[78 FR 7517, Feb. 1, 2013, as amended at 81 FR 63130, Sept. 14, 2016]
authority: 42 U.S.C. 7401
source: 57 FR 61992, Dec. 29, 1992, unless otherwise noted.