If your EGU is in this subcategory . . .
| For the following
pollutants . . .
| You must meet the following emission limits and work practice standards . . .
| Using these requirements, as appropriate (e.g., specified sampling volume or test run duration) and limitations with the test methods in Table 5 to this Subpart . . .
|
---|
1. Coal-fired unit not low rank virgin coal | a. Filterable particulate matter (PM) | Before July 6, 2027: 3.0E-2 lb/MMBtu or 3.0E-1 lb/MWh
2 | Before July 6, 2027: Collect a minimum of 1 dscm per run.
|
| | On or after July 6, 2027: 1.0E-2 lb/MMBtu or 1.0E-1 lb/MWh
2 | On or after July 6, 2027: Collect a minimum catch of 6.0 milligrams or a minimum sample volume of 4 dscm per run.
|
| OR | OR | On or after July 6, 2027 you may only demonstrate compliance with the following total non-Hg HAP metals emission limit if you request and receive approval for the use of a non-Hg HAP metals CMS under 40 CFR 63.7(f).
|
| Total non-Hg HAP metals | Before July 6, 2027: 5.0E-5 lb/MMBtu or 5.0E-1 lb/GWh
On or after July 6, 2027: 1.7E-5 lb/MMBtu or 1.7E-1 lb/GWh | Collect a minimum of 1 dscm per run.
|
| OR | OR | On or after July 6, 2027 you may only demonstrate compliance with the following individual HAP metals emissions limits if you request and receive approval for the use of a non-Hg HAP metals CMS under 40 CFR 63.7(f).
|
| Individual HAP metals: | | Collect a minimum of 3 dscm per run.
|
| Antimony (Sb) | Before July 6, 2027: 8.0E-1 lb/TBtu or 8.0E-3 lb/GWh
On or after July 6, 2027: 2.7E-1 lb/TBtu or 2.7E-3 lb/GWh
| |
| Arsenic (As) | Before July 6, 2027: 1.1E0 lb/TBtu or 2.0E-2 lb/GWh
On or after July 6, 2027: 3.7E-1 lb/TBtu or 6.7E-3 lb/GWh
| |
| Beryllium (Be) | Before July 6, 2027: 2.0E-1 lb/TBtu or 2.0E-3 lb/GWh
On or after July 6, 2027: 6.7E-2 lb/TBtu or 6.7E-4 lb/GWh
| |
| Cadmium (Cd) | Before July 6, 2027: 3.0E-1 lb/TBtu or 3.0E-3 lb/GWh
On or after July 6, 2027: 1.0E-1 lb/TBtu or 1.0E-3 lb/GWh
| |
| Chromium (Cr) | Before July 6, 2027: 2.8E0 lb/TBtu or 3.0E-2 lb/GWh
On or after July 6, 2027: 9.3E-1 lb/TBtu or 1.0E-2 lb/GWh
| |
| Cobalt (Co) | Before July 6, 2027: 8.0E-1 lb/TBtu or 8.0E-3 lb/GWh
On or after July 6, 2027: 2.7E-1 lb/TBtu or 2.7E-3 lb/GWh
| |
| Lead (Pb) | Before July 6, 2027: 1.2E0 lb/TBtu or 2.0E-2 lb/GWh
On or after July 6, 2027: 4.0E-1 lb/TBtu or 6.7E-3 lb/GWh
| |
| Manganese (Mn) | Before July 6, 2027: 4.0E0 lb/TBtu or 5.0E-2 lb/GWh
On or after July 6, 2027: 1.3E0 lb/TBtu or 1.7E-2 lb/GWh
| |
| Nickel (Ni) | Before July 6, 2027: 3.5E0 lb/TBtu or 4.0E-2 lb/GWh
On or after July 6, 2027: 1.2E0 lb/TBtu or 1.3E-2 lb/GWh
| |
| Selenium (Se) | Before July 6, 2027: 5.0E0 lb/TBtu or 6.0E-2 lb/GWh
On or after July 6, 2027: 1.7E0 lb/TBtu or 2.0E-2 lb/GWh
| |
| b. Hydrogen chloride (HCl) | 2.0E-3 lb/MMBtu or 2.0E-2 lb/MWh | For Method 26A at appendix A-8 to part 60 of this chapter, collect a minimum of 0.75 dscm per run; for Method 26, collect a minimum of 120 liters per run. For ASTM D6348-03 (Reapproved 2010)
3 or Method 320 at appendix A to part 63 of this chapter, sample for a minimum of 1 hour.
|
| OR
| | |
| Sulfur dioxide (SO2)
4 | 2.0E-1 lb/MMBtu or 1.5E0 lb/MWh | SO2 CEMS.
|
| c. Mercury (Hg) | 1.2E0 lb/TBtu or 1.3E-2 lb/GWh | LEE Testing for 30 days with a sampling period consistent with that given in section 5.2.1 of appendix A to this subpart per Method 30B at appendix A-8 to part 60 of this chapter run or Hg CEMS or sorbent trap monitoring system only.
|
| | OR
| |
| | 1.0E0 lb/TBtu or 1.1E-2 lb/GWh | LEE Testing for 90 days with a sampling period consistent with that given in section 5.2.1 of appendix A to this subpart per Method 30B run or Hg CEMS or sorbent trap monitoring system only.
|
2. Coal-fired unit low rank virgin coal | a. Filterable particulate matter (PM) | Before July 6, 2027: 3.0E-2 lb/MMBtu or 3.0E-1 lb/MWh
2
On or after July 6, 2027: 1.0E-2 lb/MMBtu or 1.0E-1 lb/MWh
2 | Before July 6, 2027: Collect a minimum of 1 dscm per run.
On or after July 6, 2027: Collect a minimum catch of 6.0 milligrams or a minimum sample volume of 4 dscm per run.
|
| OR | OR | On or after July 6, 2027 you may only demonstrate compliance with the following total non-Hg HAP metals emission limit if you request and receive approval for the use of a non-Hg HAP metals CMS under 40 CFR 63.7(f).
|
| Total non-Hg HAP metals | Before July 6, 2027: 5.0E-5 lb/MMBtu or 5.0E-1 lb/GWh
On or after July 6, 2027: 1.7E-5 lb/MMBtu or 1.7E-1 lb/GWh | Collect a minimum of 1 dscm per run.
|
| OR | OR | On or after July 6, 2027 you may only demonstrate compliance with the following individual HAP metals emissions limits if you request and receive approval for the use of a non-Hg HAP metals CMS under 40 CFR 63.7(f).
|
| Individual HAP metals: | | Collect a minimum of 3 dscm per run.
|
| Antimony (Sb) | Before July 6, 2027: 8.0E-1 lb/TBtu or 8.0E-3 lb/GWh
On or after July 6, 2027: 2.7E-1 lb/TBtu or 2.7E-3 lb/GWh
| |
| Arsenic (As) | Before July 6, 2027: 1.1E0 lb/TBtu or 2.0E-2 lb/GWh
On or after July 6, 2027: 3.7E-1 lb/TBtu or 6.7E-3 lb/GWh
| |
| Beryllium (Be) | Before July 6, 2027: 2.0E-1 lb/TBtu or 2.0E-3 lb/GWh
On or after July 6, 2027: 6.7E-2 lb/TBtu or 6.7E-4 lb/GWh
| |
| Cadmium (Cd) | Before July 6, 2027: 3.0E-1 lb/TBtu or 3.0E-3 lb/GWh
On or after July 6, 2027: 1.0E-1 lb/TBtu or 1.0E-3 lb/GWh
| |
| Chromium (Cr) | Before July 6, 2027: 2.8E0 lb/TBtu or 3.0E-2 lb/GWh
On or after July 6, 2027: 9.3E-1 lb/TBtu or 1.0E-2 lb/GWh
| |
| Cobalt (Co) | Before July 6, 2027: 8.0E-1 lb/TBtu or 8.0E-3 lb/GWh
On or after July 6, 2027: 2.7E-1 lb/TBtu or 2.7E-3 lb/GWh
| |
| Lead (Pb) | Before July 6, 2027: 1.2E0 lb/TBtu or 2.0E-2 lb/GWh
On or after July 6, 2027: 4.0E-1 lb/TBtu or 6.7E-3 lb/GWh
| |
| Manganese (Mn) | Before July 6, 2027: 4.0E0 lb/TBtu or 5.0E-2 lb/GWh
On or after July 6, 2027: 1.3E0 lb/TBtu or 1.7E-2 lb/GWh
| |
| Nickel (Ni) | Before July 6, 2027: 3.5E0 lb/TBtu or 4.0E-2 lb/GWh
On or after July 6, 2027: 1.2E0 lb/TBtu or 1.3E-2 lb/GWh
| |
| Selenium (Se) | Before July 6, 2027: 5.0E0 lb/TBtu or 6.0E-2 lb/GWh
On or after July 6, 2027: 1.7E0 lb/TBtu or 2.0E-2 lb/GWh
| |
| b. Hydrogen chloride (HCl) | 2.0E-3 lb/MMBtu or 2.0E-2 lb/MWh | For Method 26A, collect a minimum of 0.75 dscm per run; for Method 26 at appendix A-8 to part 60 of this chapter, collect a minimum of 120 liters per run. For ASTM D6348-03 (Reapproved 2010)
3 or Method 320, sample for a minimum of 1 hour.
|
| OR | OR
| |
| Sulfur dioxide (SO2)
4 | 2.0E-1 lb/MMBtu or 1.5E0 lb/MWh | SO2 CEMS.
|
| c. Mercury (Hg) | Before July 6, 2027: 4.0E0 lb/TBtu or 4.0E-2 lb/GWh
On or after July 6, 2027: 1.2E0 lb/TBtu or 1.3E-2 lb/GWh | LEE Testing for 30 days with a sampling period consistent with that given in section 5.2.1 of appendix A to this subpart per Method 30B run or Hg CEMS or sorbent trap monitoring system only.
|
3. IGCC unit | a. Filterable particulate matter (PM) | 4.0E-2 lb/MMBtu or 4.0E-1 lb/MWh
2 | Before July 6, 2027: Collect a minimum of 1 dscm per run.
On or after July 6, 2027: Collect a minimum catch of 3.0 milligrams or a minimum sample volume of 2 dscm per run.
|
| OR | OR
| |
| Total non-Hg HAP metals | 6.0E-5 lb/MMBtu or 5.0E-1 lb/GWh | Collect a minimum of 1 dscm per run.
|
| OR | OR
| |
| Individual HAP metals: | | Collect a minimum of 2 dscm per run.
|
| Antimony (Sb) | 1.4E0 lb/TBtu or 2.0E-2 lb/GWh
| |
| Arsenic (As) | 1.5E0 lb/TBtu or 2.0E-2 lb/GWh
| |
| Beryllium (Be) | 1.0E-1 lb/TBtu or 1.0E-3 lb/GWh
| |
| Cadmium (Cd) | 1.5E-1 lb/TBtu or 2.0E-3 lb/GWh
| |
| Chromium (Cr) | 2.9E0 lb/TBtu or 3.0E-2 lb/GWh
| |
| Cobalt (Co) | 1.2E0 lb/TBtu or 2.0E-2 lb/GWh
| |
| Lead (Pb) | 1.9E+2 lb/TBtu or 1.8E0 lb/GWh
| |
| Manganese (Mn) | 2.5E0 lb/TBtu or 3.0E-2 lb/GWh
| |
| Nickel (Ni) | 6.5E0 lb/TBtu or 7.0E-2 lb/GWh
| |
| Selenium (Se) | 2.2E+1 lb/TBtu or 3.0E-1 lb/GWh
| |
| b. Hydrogen chloride (HCl) | 5.0E-4 lb/MMBtu or 5.0E-3 lb/MWh | For Method 26A, collect a minimum of 1 dscm per run; for Method 26, collect a minimum of 120 liters per run. For ASTM D6348-03 (Reapproved 2010)
3 or Method 320, sample for a minimum of 1 hour.
|
| c. Mercury (Hg) | 2.5E0 lb/TBtu or 3.0E-2 lb/GWh | LEE Testing for 30 days with a sampling period consistent with that given in section 5.2.1 of appendix A to this subpart per Method 30B run or Hg CEMS or sorbent trap monitoring system only.
|
4. Liquid oil-fired unit—continental (excluding limited-use liquid oil-fired subcategory units) | a. Filterable particulate matter (PM) | 3.0E-2 lb/MMBtu or 3.0E-1 lb/MWh
2 | Collect a minimum of 1 dscm per run.
|
| OR | OR | On or after July 6, 2027 you may only demonstrate compliance with the following total non-Hg HAP metals emission limit if you request and receive approval for the use of a non-Hg HAP metals CMS under 40 CFR 63.7(f).
|
| Total HAP metals | 8.0E-4 lb/MMBtu or 8.0E-3 lb/MWh | Collect a minimum of 1 dscm per run.
|
| OR | OR | On or after July 6, 2027 you may only demonstrate compliance with the following individual HAP metals emissions limits if you request and receive approval for the use of a non-Hg HAP metals CMS under 40 CFR 63.7(f).
|
| Individual HAP metals: | | Collect a minimum of 1 dscm per run.
|
| Antimony (Sb) | 1.3E+1 lb/TBtu or 2.0E-1 lb/GWh
| |
| Arsenic (As) | 2.8E0 lb/TBtu or 3.0E-2 lb/GWh
| |
| Beryllium (Be) | 2.0E-1 lb/TBtu or 2.0E-3 lb/GWh
| |
| Cadmium (Cd) | 3.0E-1 lb/TBtu or 2.0E-3 lb/GWh
| |
| Chromium (Cr) | 5.5E0 lb/TBtu or 6.0E-2 lb/GWh
| |
| Cobalt (Co) | 2.1E+1 lb/TBtu or 3.0E-1 lb/GWh
| |
| Lead (Pb) | 8.1E0 lb/TBtu or 8.0E-2 lb/GWh
| |
| Manganese (Mn) | 2.2E+1 lb/TBtu or 3.0E-1 lb/GWh
| |
| Nickel (Ni) | 1.1E+2 lb/TBtu or 1.1E0 lb/GWh
| |
| Selenium (Se) | 3.3E0 lb/TBtu or 4.0E-2 lb/GWh
| |
| Mercury (Hg) | 2.0E-1 lb/TBtu or 2.0E-3 lb/GWh | For Method 30B sample volume determination (Section 8.2.4), the estimated Hg concentration should nominally be <
1/2 the standard.
|
| b. Hydrogen chloride (HCl) | 2.0E-3 lb/MMBtu or 1.0E-2 lb/MWh | For Method 26A, collect a minimum of 1 dscm per run; for Method 26, collect a minimum of 120 liters per run. For ASTM D6348-03 (Reapproved 2010)
3 or Method 320, sample for a minimum of 1 hour.
|
| c. Hydrogen fluoride (HF) | 4.0E-4 lb/MMBtu or 4.0E-3 lb/MWh | For Method 26A, collect a minimum of 1 dscm per run; for Method 26, collect a minimum of 120 liters per run. For ASTM D6348-03 (Reapproved 2010)
3 or Method 320, sample for a minimum of 1 hour.
|
5. Liquid oil-fired unit—non-continental (excluding limited-use liquid oil-fired subcategory units) | a. Filterable particulate matter (PM) | 3.0E-2 lb/MMBtu or 3.0E-1 lb/MWh
2 | Collect a minimum of 1 dscm per run.
|
| OR | OR | On or after July 6, 2027 you may only demonstrate compliance with the following total non-Hg HAP metals emission limit if you request and receive approval for the use of a non-Hg HAP metals CMS under 40 CFR 63.7(f).
|
| Total HAP metals | 6.0E-4 lb/MMBtu or 7.0E-3 lb/MWh | Collect a minimum of 1 dscm per run.
|
| OR | OR | On or after July 6, 2027 you may only demonstrate compliance with the following individual HAP metals emissions limits if you request and receive approval for the use of a non-Hg HAP metals CMS under 40 CFR 63.7(f).
|
| Individual HAP metals: | | Collect a minimum of 2 dscm per run.
|
| Antimony (Sb) | 2.2E0 lb/TBtu or 2.0E-2 lb/GWh
| |
| Arsenic (As) | 4.3E0 lb/TBtu or 8.0E-2 lb/GWh
| |
| Beryllium (Be) | 6.0E-1 lb/TBtu or 3.0E-3 lb/GWh
| |
| Cadmium (Cd) | 3.0E-1 lb/TBtu or 3.0E-3 lb/GWh
| |
| Chromium (Cr) | 3.1E+1 lb/TBtu or 3.0E-1 lb/GWh
| |
| Cobalt (Co) | 1.1E+2 lb/TBtu or 1.4E0 lb/GWh
| |
| Lead (Pb) | 4.9E0 lb/TBtu or 8.0E-2 lb/GWh
| |
| Manganese (Mn) | 2.0E+1 lb/TBtu or 3.0E-1 lb/GWh
| |
| Nickel (Ni) | 4.7E+2 lb/TBtu or 4.1E0 lb/GWh
| |
| Selenium (Se) | 9.8E0 lb/TBtu or 2.0E-1 lb/GWh
| |
| Mercury (Hg) | 4.0E-2 lb/TBtu or 4.0E-4 lb/GWh | For Method 30B sample volume determination (Section 8.2.4), the estimated Hg concentration should nominally be <
1/2 the standard.
|
| b. Hydrogen chloride (HCl) | 2.0E-4 lb/MMBtu or 2.0E-3 lb/MWh | For Method 26A, collect a minimum of 1 dscm per run; for Method 26, collect a minimum of 120 liters per run. For ASTM D6348-03 (Reapproved 2010)
3 or Method 320, sample for a minimum of 2 hours.
|
| c. Hydrogen fluoride (HF) | 6.0E-5 lb/MMBtu or 5.0E-4 lb/MWh | For Method 26A, collect a minimum of 3 dscm per run. For ASTM D6348-03 (Reapproved 2010)
3 or Method 320, sample for a minimum of 2 hours.
|
6. Solid oil-derived fuel-fired unit | a. Filterable particulate matter (PM) | 8.0E-3 lb/MMBtu or 9.0E-2 lb/MWh
2 | Before July 6, 2027: Collect a minimum of 1 dscm per run.
On or after July 6, 2027: Collect a minimum catch of 6.0 milligrams or a minimum sample volume of 4 dscm per run.
|
| OR | OR | On or after July 6, 2027 you may only demonstrate compliance with the following total non-Hg HAP metals emission limit if you request and receive approval for the use of a non-Hg HAP metals CMS under 40 CFR 63.7(f).
|
| Total non-Hg HAP metals | 4.0E-5 lb/MMBtu or 6.0E-1 lb/GWh | Collect a minimum of 1 dscm per run.
|
| OR | OR | On or after July 6, 2027 you may only demonstrate compliance with the following individual HAP metals emissions limits if you request and receive approval for the use of a non-Hg HAP metals CMS under 40 CFR 63.7(f).
|
| Individual HAP metals: | | Collect a minimum of 3 dscm per run.
|
| Antimony (Sb) | 8.0E-1 lb/TBtu or 7.0E-3 lb/GWh
| |
| Arsenic (As) | 3.0E-1 lb/TBtu or 5.0E-3 lb/GWh
| |
| Beryllium (Be) | 6.0E-2 lb/TBtu or 5.0E-4 lb/GWh
| |
| Cadmium (Cd) | 3.0E-1 lb/TBtu or 4.0E-3 lb/GWh
| |
| Chromium (Cr) | 8.0E-1 lb/TBtu or 2.0E-2 lb/GWh
| |
| Cobalt (Co) | 1.1E0 lb/TBtu or 2.0E-2 lb/GWh
| |
| Lead (Pb) | 8.0E-1 lb/TBtu or 2.0E-2 lb/GWh
| |
| Manganese (Mn) | 2.3E0 lb/TBtu or 4.0E-2 lb/GWh
| |
| Nickel (Ni) | 9.0E0 lb/TBtu or 2.0E-1 lb/GWh
| |
| Selenium (Se) | 1.2E0 lb/TBtu or 2.0E-2 lb/GWh
| |
| b. Hydrogen chloride (HCl) | 5.0E-3 lb/MMBtu or 8.0E-2 lb/MWh | For Method 26A, collect a minimum of 0.75 dscm per run; for Method 26, collect a minimum of 120 liters per run. For ASTM D6348-03 (Reapproved 2010)
3 or Method 320, sample for a minimum of 1 hour.
|
| OR | OR
| |
| Sulfur dioxide (SO2)
4 | 3.0E-1 lb/MMBtu or 2.0E0 lb/MWh | SO2 CEMS.
|
| c. Mercury (Hg) | 2.0E-1 lb/TBtu or 2.0E-3 lb/GWh | LEE Testing for 30 days with a sampling period consistent with that given in section 5.2.1 of appendix A to this subpart per Method 30B run or Hg CEMS or sorbent trap monitoring system only.
|
7. Eastern Bituminous Coal Refuse (EBCR)-fired unit | a. Filterable particulate matter (PM) | Before July 6, 2027: 3.0E-2 lb/MMBtu or 3.0E-1 lb/MWh
2
On or after July 6, 2027: 1.0E-2 lb/MMBtu or 1.0E-1 lb/MWh
2 | Before July 6, 2027: Collect a minimum of 1 dscm per run.
On or after July 6, 2027: Collect a minimum catch of 6.0 milligrams or a minimum sample volume of 4 dscm per run.
|
| OR | OR | On or after July 6, 2027 you may only demonstrate compliance with the following total non-Hg HAP metals emission limit if you request and receive approval for the use of a non-Hg HAP metals CMS under 40 CFR 63.7(f).
|
| Total non-Hg HAP metals | Before July 6, 2027: 5.0E-5 lb/MMBtu or 5.0E-1 lb/GWh
On or after July 6, 2027: 1.7E-5 lb/MMBtu or 1.7E-1 lb/GWh | Collect a minimum of 1 dscm per run.
|
| OR | OR | On or after July 6, 2027 you may only demonstrate compliance with the following individual HAP metals emissions limits if you request and receive approval for the use of a non-Hg HAP metals CMS under 40 CFR 63.7(f).
|
| Individual HAP metals: | | Collect a minimum of 3 dscm per run.
|
| Antimony (Sb) | Before July 6, 2027: 8.0E-1 lb/TBtu or 8.0E-3 lb/GWh
On or after July 6, 2027: 2.7E-1 lb/TBtu or 2.7E-3 lb/GWh
| |
| Arsenic (As) | Before July 6, 2027: 1.1E0 lb/TBtu or 2.0E-2 lb/GWh
On or after July 6, 2027: 3.7E-1 lb/TBtu or 6.7E-3 lb/GWh
| |
| Beryllium (Be) | Before July 6, 2027: 2.0E-1 lb/TBtu or 2.0E-3 lb/GWh
On or after July 6, 2027: 6.7E-2 lb/TBtu or 6.7E-4 lb/GWh
| |
| Cadmium (Cd) | Before July 6, 2027: 3.0E-1 lb/TBtu or 3.0E-3 lb/GWh
On or after July 6, 2027: 1.0E-1 lb/TBtu or 1.0E-3 lb/GWh
| |
| Chromium (Cr) | Before July 6, 2027: 2.8E0 lb/TBtu or 3.0E-2 lb/GWh
On or after July 6, 2027: 9.3E-1 lb/TBtu or 1.0E-2 lb/GWh
| |
| Cobalt (Co) | Before July 6, 2027: 8.0E-1 lb/TBtu or 8.0E-3 lb/GWh
On or after July 6, 2027: 2.7E-1 lb/TBtu or 2.7E-3 lb/GWh
| |
| Lead (Pb) | Before July 6, 2027: 1.2E0 lb/TBtu or 2.0E-2 lb/GWh
On or after July 6, 2027: 4.0E-1 lb/TBtu or 6.7E-3 lb/GWh
| |
| Manganese (Mn) | Before July 6, 2027: 4.0E0 lb/TBtu or 5.0E-2 lb/GWh
On or after July 6, 2027: 1.3E0 lb/TBtu or 1.7E-2 lb/GWh
| |
| Nickel (Ni) | Before July 6, 2027: 3.5E0 lb/TBtu or 4.0E-2 lb/GWh
On or after July 6, 2027: 1.2E0 lb/TBtu or 1.3E-2 lb/GWh
| |
| Selenium (Se) | Before July 6, 2027: 5.0E0 lb/TBtu or 6.0E-2 lb/GWh
On or after July 6, 2027: 1.7E0 lb/TBtu or 2.0E-2 lb/GWh
| |
| b. Hydrogen chloride (HCl) | 4.0E-2 lb/MMBtu or 4.0E-1 lb/MWh | For Method 26A at appendix A-8 to part 60 of this chapter, collect a minimum of 0.75 dscm per run; for Method 26, collect a minimum of 120 liters per run. For ASTM D6348-03 (Reapproved 2010)
3 or Method 320 at appendix A to part 63 of this chapter, sample for a minimum of 1 hour.
|
| OR
| | |
| Sulfur dioxide (SO2)
4 | 6E-1 lb/MMBtu or 9E0 lb/MWh | SO2 CEMS.
|
| c. Mercury (Hg) | 1.2E0 lb/TBtu or 1.3E-2 lb/GWh | LEE Testing for 30 days with a sampling period consistent with that given in section 5.2.1 of appendix A to this subpart per Method 30B at appendix A-8 to part 60 of this chapter run or Hg CEMS or sorbent trap monitoring system only.
|
| OR
| | |
| | 1.0E0 lb/TBtu or 1.1E-2 lb/GWh | LEE Testing for 90 days with a sampling period consistent with that given in section 5.2.1 of appendix A to this subpart per Method 30B run or Hg CEMS or sorbent trap monitoring system only.
|