Regulations last checked for updates: Nov 22, 2024

Title 40 - Protection of Environment last revised: Nov 20, 2024
Appendix Appendix A1 - Appendix A1 to Subpart F of Part 82—Generic Maximum Contaminant Levels
Contaminant Reporting units
Air and Other Non-condensables1.5% by volume @ 25 °C (N/A for refrigerants used in low-pressure appliances 1).
Water10 ppm by weight 20 ppm by weight (for refrigerants used in low-pressure appliances 1).
Other Impurities Including Refrigerant0.50% by weight.
High boiling residue0.01% by volume.
Particulates/solidsvisually clean to pass.
Acidity1.0 ppm by weight.
Chlorides (chloride level for pass/fail is 3ppm)No visible turbidity.

1 Low-pressure appliances means an appliance that uses a refrigerant with a liquid phase saturation pressure below 45 psia at 104 °F.

Blend Compositions (Where Applicable)

Nominal
composition
(by weight%)
Allowable
composition
(by weight%)
Component constitutes 25% or more±2.0
Component constitutes less than 25% but greater than 10%±1.0
Component constitutes less than or equal to 10%±0.5
[69 FR 11988, Mar. 12, 2004]
authority: 42 U.S.C. 7414,7601,7671
source: 57 FR 33787, July 30, 1992, unless otherwise noted.