End-use
| Substitute
| Decision
| Comments
|
---|
CFC-11 centrifugal chillers (retrofit) | HCFC-141b | Unacceptable | Has a high ODP relative to other alternatives.
|
CFC-12 centrifugal chillers (retrofit) | HCFC-22/HFC-142b/CFC-12 | Unacceptable | As a blend of both Class I and Class II substances, it has a higher ODP than use of Class II substances.
|
| Hydrocarbon blend A | Unacceptable | Flammability is a serious concern. Data have not been submitted to demonstrate it can used safely in this end-use.
|
CFC-11, CFC-12, CFC-113, CFC-114, R-500 centrifugal chillers (new equipment/NIKs) | HCFC-22/HFC-142b/CFC-12 | Unacceptable | As a blend of both Class I and Class II substances, it has a higher ODP than use of Class II substances.
|
| Hydrocabon blend A | Unacceptable | Flammability is a serious concern. Data have not been submitted to demonstrate it can be used safely in this end-use.
|
| HCFC-141b | Unacceptable | Has a high ODP relative to other alternatives.
|
CFC-12 reciprocating chillers (retrofit) | HCFC-22/HFC-142b/CFC-12 | Unacceptable | As a blend of both Class I and Class II substances, it has a higher ODP than use of Class II substances.
|
| Hydrocarbon blend A | Unacceptable | Flammability is a serious concern. Data have not been submitted to demonstrate it can be used safely in this end-use.
|
CFC-12 reciprocating chillers (new equipment/NIKs) | HCFC-22/HFC-142b/CFC-12 | Unacceptable | As a blend of both Class I and Class II substances, it has a higher ODP than use of Class II substances.
|
| Hydrocarbon blend A | Unacceptable | Flammability is a serious concern. Data have not been submitted to demonstrate it can be used safely in this end-use.
|
CFC-11, CFC-12, R-502 industrial process refrigeration (retrofit) | HCFC-22/HFC-142b/CFC-12 | Unacceptable | As a blend of both Class I and Class II substances, it has a higher ODP than use of Class II substances.
|
CFC-11, CFC-12, R-502 industrial process refrigeration (new equipment/NIKs) | HCFC-22/HFC-142b/CFC-12 | Unacceptable | As a blend of both Class I and Class II substances, it has a higher ODP than use of Class II substances.
|
CFC-12, R-502 ice skating rinks (retrofit) | HCFC-22/HFC-142b/CFC-12 | Unacceptable | As a blend of both Class I and Class II substances, it has a higher ODP than use of Class II substances.
|
| Hydrocarbon blend A | Unacceptable | Flammability is a serious concern. Data have not been submitted to demonstrate it can be used safely in this end-use.
|
CFC-12, R-502 ice skating rinks (new equipment/NIKs) | HCFC-22/HFC-142b/CFC-12 | Unacceptable | As a blend of both Class I and Class II substances, it has a higher ODP than use of Class II substances.
|
| Hydrocarbon blend A | Unacceptable | Flammability is a serious concern. Data have not been submitted to demonstrate it can be used safely in this end-use.
|
CFC-12, R-502 cold storage warehouses (retrofit) | HCFC-22/HFC-142b/CFC-12 | Unacceptable | As a blend of both Class I and Class II substances, it has a higher ODP than use of Class II substances.
|
| Hydrocarbon blend A | Unacceptable | Flammability is a serious concern. Data have not been submitted to demonstrate it can be used safely in this end-use.
|
CFC-12, R-502 cold storage warehouses (new equipment/NIKs) | HCFC-22/HFC-142b/CFC-12 | Unacceptable | As a blend of both Class I and Class II substances, it has a higher ODP than use of Class II substances.
|
| Hydrocarbon blend A | Unacceptable | Flammability is a serious concern. Data have not been submitted to demonstrate it can be used safely in this end-use.
|
CFC-12, R-500, R-502 refrigerated transport (retrofit) | HCFC-22/HFC-142b/CFC-12 | Unacceptable | As a blend of both Class I and Class II substances, it has a higher ODP than use of Class II substances.
|
| Hydrocarbon blend A | Unacceptable | Flammability is a serious concern. Data have not been submitted to demonstrate it can be used safely in this end-use.
|
CFC-12, R-500, R-502 refrigerated transport (new equipment/NIKs) | HCFC-22/HFC-142b/CFC-12 | Unacceptable | As a blend of both Class I and Class II substances, it has a higher ODP than use of Class II substances.
|
| Hydrocarbon blend A | Unacceptable | Flammability is a serious concern. Data have not been submitted to demonstrate it can be used safely in this end-use.
|
CFC-12, R-502 retail food refrigeration (retrofit) | HCFC-22/HFC-142b/CFC-12 | Unacceptable | As a blend of both Class I and Class II substances, it has a higher ODP than use of Class II substances.
|
| Hydrocarbon blend A | Unacceptable | Flammability is a serious concern. Data have not been submitted to demonstrate it can be used safely in this end-use.
|
CFC-12, R-502 retail food refrigeration (new equipment/NIKs) | HCFC-22/HFC-142b/CFC-12 | Unacceptable | As a blend of both Class I and Class II substances, it has a higher ODP than use of Class II substances.
|
| Hydrocarbon blend A | Unacceptable | Flammability is a serious concern. Data have not been submitted to demonstrate it can be used safely in this end-use.
|
CFC-12, R-502 commercial ice machines (retrofit) | HCFC-22/HFC-142b/CFC-12 | Unacceptable | As a blend of both Class I and Class II substances, it has a higher ODP than use of Class II substances.
|
| Hydrocarbon blend A | Unacceptable | Flammability is a serious concern. Data have not been submitted to demonstrate it can be used safely in this end-use.
|
CFC-12, R-502 commercial ice machines (new equipment/NIKs) | HCFC-22/HFC-142b/CFC-12 | Unacceptable | As a blend of both Class I and Class II substances, it has a higher ODP than use of Class II substances.
|
| Hydrocarbon blend A | Unacceptable | Flammability is a serious concern. Data have not been submitted to demonstrate it can be used safely in this end-use.
|
CFC-12 vending machines (retrofit) | HCFC-22/HFC-142b/CFC-12 | Unacceptable | As a blend of both Class I and Class II substances, it has a higher ODP than use of Class II substances.
|
| Hydrocarbon blend A | Unacceptable | Flammability is a serious concern. Data have not been submitted to demonstrate it can be used safely in this end-use.
|
CFC-12 vending machines (new equipment/NIKs) | HCFC-22/HFC-142b/CFC-12 | Unacceptable | As a blend of both Class I and Class II substances, it has a higher ODP than use of Class II substances.
|
| Hydrocarbon blend A | Unacceptable | Flammability is a serious concern. Data have not been submitted to demonstrate it can be used safely in this end-use.
|
CFC-12, water coolers (retrofit) | HCFC-22/HFC-142b/CFC-12 | Unacceptable | As a blend of both Class I and Class II substances, it has a higher ODP than use of Class II substances.
|
| Hydrocarbon blend A | Unacceptable | Flammability is a serious concern. Data have not been submitted to demonstrate it can be used safely in this end-use.
|
CFC-12, water coolers (New equipment/NIKs) | HCFC-22/HFC-142b/CFC-12 | Unacceptable | As a blend of both Class I and Class II substances, it has a higher ODP than use of Class II substances.
|
| Hydrocarbon blend A | Unacceptable | Flammability is a serious concern. Data have not been submitted to demonstrate it can be used safely in this end-use.
|
CFC-12, household refrigerators (retrofit) | HCFC-22/HFC-142b/CFC-12 | Unacceptable | As a blend of both Class I and Class II substances, it has a higher ODP than use of Class II substances.
|
| Hydrocarbon blend A | Unacceptable | Flammability is a serious concern. Data have not been submitted to demonstrate it can be used safely in this end-use.
|
CFC-12, household refrigerators (new equipment/NIKs) | HCFC-22/HFC-142b/CFC-12 | Unacceptable | As a blend of both Class I and Class II substances, it has a higher ODP than use of Class II substances.
|
| Hydrocarbon blend A | Unacceptable | Flammability is a serious concern. Data have not been submitted to demonstrate it can be used safely in this end-use.
|
CFC-12, R-502 household freezers (retrofit) | HCFC-22/HFC-142b/CFC-12 | Unacceptable | As a blend of both Class I and Class II substances, it has a higher ODP than use of Class II substances.
|
| Hydrocarbon blend A | Unacceptable | Flammability is a serious concern. Data have not been submitted to demonstrate it can be used safely in this end-use.
|
CFC-12, 502 household freezers (new equipment/NIKs) | HCFC-22/HFC-142b/CFC-12 | Unacceptable | As a blend of both Class I and Class II substances, it has a higher ODP than use of Class II substances.
|
| Hydrocarbon blend A | Unacceptable | Flammability is a serious concern. Data have not been submitted to demonstrate it can be used safely in this end-use.
|
CFC-12, R-500 residential dehumidifiers (retrofit) | HCFC-22/HFC-142b/CFC-12 | Unacceptable | As a blend of both Class I and Class II substances, it has a higher ODP than use of Class II substances.
|
| Hydrocarbon blend A | Unacceptable | Flammability is a serious concern. Data have not been submitted to demonstrate it can be used safely in this end-use.
|
CFC-12, R-500 residential dehumidifiers (new equipment/NIKs) | HCFC-22/HFC-142b/CFC-12 | Unacceptable | As a blend of both Class I and Class II substances, it has a higher ODP than use of Class II substances.
|
| Hydrocarbon blend A | Unacceptable | Flammability is a serious concern. Data have not been submitted to demonstrate it can be used safely in this end-use.
|
CFC-12, motor vehicle air conditioners (retrofit) | HCFC-22/HFC-142b/CFC-12 | Unacceptable | As a blend of both Class I and Class II substances, it has a higher ODP than use of Class II substances.
|
| Hydrocarbon blend A | Unacceptable | Flammability is a serious concern. Data have not been submitted to demonstrate it can be used safely in this end-use.
|
CFC-12, motor vehicle air conditioners (new equipment/NIKs) | HCFC-22/HFC-142b/CFC-12 | Unacceptable | As a blend of both Class I and Class II substances, it has a higher ODP than use of Class II substances.
|
| Hydrocarbon blend A | Unacceptable | Flammability is a serious concern. Data have not been submitted to demonstrate it can be sued safely in this end-use. |