(a) Any new source subject to this subpart must achieve the following performance standards:
Pollutant or pollutant property
| Maximum for any 1 day
| Monthly average shall not exceed
|
---|
| Milligrams per liter (mg/l)
|
Cadmium (T) | 0.11 | 0.07
|
Chromium (T) | 2.77 | 1.71
|
Copper (T) | 3.38 | 2.07
|
Lead (T) | 0.69 | 0.43
|
Nickel (T) | 3.98 | 2.38
|
Silver (T) | 0.43 | 0.24
|
Zinc (T) | 2.61 | 1.48
|
Cyanide (T) | 1.20 | 0.65
|
TTO | 2.13 | |
Oil and Grease | 52 | 26
|
TSS | 60 | 31
|
pH | (
1) | (
1)
|
(b) Alternatively, for industrial facilities with cyanide treatment, and upon agreement between a source subject to those limits and the pollution control authority, the following amenable cyanide limit may apply in place of the total cyanide limit specified in paragraph (a) of this section:
Pollutant or pollutant property
| Maximum for any 1 day
| Monthly average shall not exceed
|
---|
| Milligrams per liter (mg/l)
|
Cyanide (A) | 0.86 | 0.32 |
(c) No user subject to the provisions of this subpart shall augment the use of process wastewater or otherwise dilute the wastewater as a partial or total substitute for adequate treatment to achieve compliance with this limitation.
[48 FR 32485, July 15, 1983; 48 FR 43682, Sept. 26, 1983]
authority: Secs. 301, 304(b), (c), (e), and (g), 306(b) and (c), 307(b) and (c), 308 and 501 of the Clean Water Act (the Federal Water Pollution Control Act Amendments of 1971, as amended by the Clean Water Act of 1977) (the “Act”);
33 U.S.C. 1311,
1314,
e,
and,
1316,
1317,
1318; 86 Stat. 816, Pub. L. 92-500; 91 Stat. 1567, Pub. L. 95-217
source: 48 FR 32485, July 15, 1983, unless otherwise noted.
cite as: 40 CFR 433.16