Appendix - Table 2B to Subpart Ce of Part 60—Emissions Limits for Small HMIWI Which Meet the Criteria Under § 60.33e(b)(2)
Pollutant Units
(7 percent oxygen, dry basis)
HMIWI Emissions limits Averaging time 1 Method for demonstrating compliance 2
Particulate mattermg/dscm (gr/dscf)87 (0.038)3-run average (1-hour minimum sample time per run)EPA Reference Method 5 of appendix A-3 of part 60, or EPA Reference Method 26A or 29 of appendix A-8 of part 60.
Carbon monoxideppmv203-run average (1-hour minimum sample time per run)EPA Reference Method 10 or 10B of appendix A-4 of part 60.
Dioxins/furansng/dscm total dioxins/furans (gr/10 9 dscf) or ng/dscm TEQ (gr/10 9 dscf)240 (100) or 5.1 (2.2)3-run average (4-hour minimum sample time per run)EPA Reference Method 23 of appendix A-7 of part 60.
Hydrogen chlorideppmv8103-run average (1-hour minimum sample time per run)EPA Reference Method 26 or 26A of appendix A-8 of part 60.
Sulfur dioxideppmv553-run average (1-hour minimum sample time per run)EPA Reference Method 6 or 6C of appendix A-4 of part 60.
Nitrogen oxidesppmv1303-run average (1-hour minimum sample time per run)EPA Reference Method 7 or 7E of appendix A-4 of part 60.
Leadmg/dscm (gr/10 3 dscf)0.50 (0.22)3-run average (1-hour minimum sample time per run)EPA Reference Method 29 of appendix A-8 of part 60.
Cadmiummg/dscm (gr/10 3 dscf)0.11 (0.048)3-run average (1-hour minimum sample time per run)EPA Reference Method 29 of appendix A-8 of part 60.
Mercurymg/dscm (gr/10 3 dscf)0.0051 (0.0022)3-run average (1-hour minimum sample time per run)EPA Reference Method 29 of appendix A-8 of part 60.

1 Except as allowed under § 60.56c(c) for HMIWI equipped with CEMS.

2 Does not include CEMS and approved alternative non-EPA test methods allowed under § 60.56c(b).

[74 FR 51407, Oct. 6, 2009]
authority: 42 U.S.C. 7401