Regulations last checked for updates: Nov 22, 2024

Title 40 - Protection of Environment last revised: Nov 20, 2024
Appendix - Table 2 to Subpart CCCC of Part 60—Operating Limits for Wet Scrubbers
For these operating parameters You must establish these operating limits And monitoring using these minimum frequencies
Data measurement Data recording Averaging time
Charge rateMaximum charge rateContinuousEvery hourDaily (batch units) 3-hour rolling (continuous and intermittent units). 1
Pressure drop across the wet scrubber or amperage to wet scrubberMinimum pressure drop or amperageContinuousEvery 15 minutes3-hour rolling. 1
Scrubber liquor flow rateMinimum flow rateContinuousEvery 15 minutes3-hour rolling. 1
Scrubber liquor pHMinimum pHContinuousEvery 15 minutes3-hour rolling. 1

1 Calculated each hour as the average of the previous 3 operating hours.

authority: 42 U.S.C. 7401
source: 36 FR 24877, Dec. 23, 1971, unless otherwise noted.