For the air pollutant
| You must meet this emission limitation
1
| Using this averaging time
2
| And determining compliance using this method
2
|
---|
Liquid/gas
| Solids
|
---|
Cadmium | 0.023 milligrams per dry standard cubic meter | Biomass—0.0014 milligrams per dry standard cubic meter. Coal—0.0017 milligrams per dry standard cubic meter | 3-run average (collect a minimum volume of 4 dry standard cubic meters per run) | Performance test (Method 29 at 40 CFR part 60, appendix A-8). Use ICPMS for the analytical finish.
|
Carbon monoxide | 35 parts per million dry volume | Biomass—240 parts per million dry volume. Coal—95 parts per million dry volume | 3-run average (1 hour minimum sample time per run) | Performance test (Method 10 at 40 CFR part 60, appendix A-4).
|
Dioxin/furans (Total Mass Basis) | No Total Mass Basis limit, must meet the toxic equivalency basis limit below | Biomass—0.52 nanograms per dry standard cubic meter. Coal—5.1 nanograms per dry standard cubic meter | 3-run average (collect a minimum volume of 4 dry standard cubic meters) | Performance test (Method 23 at 40 CFR part 60, appendix A-7).
|
Dioxins/furans (toxic equivalency basis) | 0.093 nanograms per dry standard cubic meter | Biomass—0.076 nanograms per dry standard cubic meter.
3 Coal—0.075 nanograms per dry standard cubic meter | 3-run average (collect a minimum volume of 4 dry standard cubic meters per run) | Performance test (Method 23 of appendix A-7 of this part).
|
Fugitive ash | Visible emissions for no more than 5 percent of the hourly observation period | Three 1-hour observation periods | Visible emission test (Method 22 at 40 CFR part 60, appendix A-7) | Fugitive ash.
|
Hydrogen chloride | 14 parts per million dry volume | Biomass—0.20 parts per million dry volume. Coal—58 parts per million dry volume | 3-run average (For Method 26, collect a minimum volume of 360 liters per run. For Method 26A, collect a minimum volume of 3 dry standard cubic meters per run) | Performance test (Method 26 or 26A at 40 CFR part 60, appendix A-8).
|
Lead | 0.096 milligrams per dry standard cubic meter | Biomass—0.014 milligrams per dry standard cubic meter. Coal—0.057 milligrams per dry standard cubic meter | 3-run average (collect a minimum volume of 4 dry standard cubic meters per run) | Performance test (Method 29 at 40 CFR part 60, appendix A-8). Use ICPMS for the analytical finish.
|
Mercury | 0.00056 milligrams per dry standard cubic meter | Biomass—0.0022 milligrams per dry standard cubic meter. Coal—0.013 milligrams per dry standard cubic meter | 3-run average (collect enough volume to meet an in-stack detection limit data quality objective of 0.03 ug/dscm) | Performance test (Method 29 or 30B at 40 CFR part 60, appendix A-8) or ASTM D6784-02 (Reapproved 2008).
3
|
Nitrogen oxides | 76 parts per million dry volume | Biomass—290 parts per million dry volume. Coal—460 parts per million dry volume | 3-run average (for Method 7E, 1 hour minimum sample time per run) | Performance test (Method 7 or 7E at 40 CFR part 60, appendix A-4).
|
Particulate matter (filterable) | 110 milligrams per dry standard cubic meter | Biomass—5.1 milligrams per dry standard cubic meter. Coal—130 milligrams per dry standard cubic meter | 3-run average (collect a minimum volume of 1 dry standard cubic meter per run) | Performance test (Method 5 or 29 at 40 CFR part 60, appendix A-3 or appendix A-8).
|
Sulfur dioxide | 720 parts per million dry volume | Biomass—7.3 parts per million dry volume. Coal—850 parts per million dry volume | 3-run average (for Method 6, collect a minimum of 60 liters, for Method 6C, 1 hour minimum sample time per run) | Performance test (Method 6 or 6C at 40 CFR part 60, appendix A-4).
|