Regulations last checked for updates: Nov 22, 2024

Title 40 - Protection of Environment last revised: Nov 20, 2024
Appendix - Table 2 to Subpart EEEE of Part 60—Operating Limits for Incinerators and Wet Scrubbers

As stated in § 60.2916, you must comply with the following:

For these operating
parameters
You must establish these operating limits And monitoring using these minimum frequencies
Data measurement Data recording Averaging time
1. Charge rateMaximum charge rateContinuousEvery hourDaily for batch units. 3-hour rolling for continuous and intermittent units a.
2. Pressure drop across the wet scrubber or amperage to wet scrubberMinimum pressure drop or amperageContinuousEvery 15 minutes3-hour rolling a.
3. Scrubber liquor flow rateMinimum flow rateContinuousEvery 15 minutes3-hour rolling a.
4. Scrubber liquor pHMinimum pHContinuousEvery 15 minutes3-hour rolling a.

a Calculated each hour as the average of the previous 3 operating hours.

authority: 42 U.S.C. 7401
source: 36 FR 24877, Dec. 23, 1971, unless otherwise noted.