For the
operating parameter applicable to you, as specified in Table 2 . . .
| You must establish the following operating parameter limit . . .
| And you must monitor, record, and demonstrate continuous compliance using these minimum frequencies . . .
|
---|
Data measurement
| Data
recording
| Data
averaging period for compliance
|
---|
Absorbers
|
1. Exit temperature of the absorbing liquid | Maximum temperature | Continuous | Every 15 minutes | 3-hour block average
|
2. Exit specific gravity | Exit specific gravity range | Continuous | Every 15 minutes | 3-hour block average
|
Boilers or process heaters
|
(with a design heat input capacity <44MW and vent stream is not introduced with or as the primary fuel)
|
3. Firebox temperature | Minimum firebox temperature | Continuous | Every 15 minutes | 3-hour block average
|
Catalytic incinerators
|
4. Temperature in gas stream immediately before the catalyst bed | Minimum temperature | Continuous | Every 15 minutes | 3-hour block average
|
5. Temperature difference between the catalyst bed inlet and the catalyst bed outlet | Minimum temperature difference | Continuous | Every 15 minutes | 3-hour block average
|
Carbon adsorbers
|
6. Total regeneration stream mass flow during carbon bed regeneration cycle(s) | Minimum mass flow during carbon bed regeneration cycle(s) | Continuously during regeneration | Every 15 minutes during regeneration cycle | Total flow for each regeneration cycle
|
7. Total regeneration stream volumetric flow during carbon bed regeneration cycle(s) | Minimum volumetric flow during carbon bed regeneration cycle(s) | Continuously during regeneration | Every 15 minutes during regeneration cycle | Total flow for each regeneration cycle
|
8. Temperature of the carbon bed after regeneration [and within 15 minutes of completing any cooling cycle(s)] | Maximum temperature of the carbon bed after regeneration | Continuously during regeneration and for 15 minutes after completing any cooling cycle(s) | Every 15 minutes during regeneration cycle (including any cooling cycle) | Average of regeneration cycle
|
9. Breakthrough | As defined in § 60.701a | As required by § 60.703a(a)(6)(iii)(B) | Each monitoring event | N/A
|
Condensers
|
10. Exit (product side) temperature | Maximum temperature | Continuous | Every 15 minutes | 3-hour block average
|
Scrubbers for halogenated vent streams
|
11. pH of scrubber effluent | Minimum pH | Continuous | Every 15 minutes | 3-hour block average
|
12. Influent liquid flow | Minimum inlet liquid flow | Continuous | Every 15 minutes | 3-hour block average
|
13. Influent liquid flow rate and gas stream flow rate | Minimum influent liquid-to-gas ratio | Continuous | Every 15 minutes | 3-hour block average
|
Thermal incinerators
|
14. Firebox temperature | Minimum firebox temperature | Continuous | Every 15 minutes | 3-hour block average
|
Control devices other than an incinerator, boiler, process heater, or flare; or recovery devices other than an absorber, condenser, or carbon adsorber
|
15. As specified by the Administrator | As specified by the Administrator | As specified by the Administrator | As specified by the Administrator | As specified by the Administrator |